Plan Review Notes
Plan Review Notes For Permit 08050795
Permit Number 08050795
Review Stop B
Sequence Number 1
Notes
Date Text
2008-07-02 10:21:53REVIEW IN PROGRESS.
  
 BUILDING PLAN REVIEW
 PERMIT: 08050795
 ADD: 706 8TH STREET
 CONT: YOUCHAK & YOUCHAK INC.
 TEL: (561)832-3800
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)WHAT IS THE CORRECT ADDRESS FOR THE PROJECT IS IT
 814 DIVISION AVE OR IS IT 706 8TH STREET. THE ADDRESS
 ON THE APPLICATION IS DIFFERENT FROM THE ONE ON THE
 DRAWINGS. CLARIFY. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED. 106.1.1.
  
 3) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS
 & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 4)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 5)109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAIL TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 6)THE DRAWINGS INDICATE THE MAJORITY OF THE ROOMS FOR
 THIS BUILDING AS EDUCATIONAL ROOMS, BUT DID NOT CLEARLY
 INDICATE THE LEVEL OF EDUCATION. ARE THE EDUCATIONAL
 ROOMS USED FOR STUDENTS BELOW THE 12TH GRADE OR ABOVE?
 FBC 304 - 305 CLASSROOMS AND LABORATORIES FOR STUDENTS
 ABOVE THE 12TH GRADE LEVEL ARE CLASSIFIED IN GROUP B.
 THE AGE OF THE STUDENTS WHO WILL BE USING THIS FACILITY
 SHALL BE STATED ON THE PLANS FOR A BETTER UNDERSTANDING
 OF THE BUILDING USE. INFORMATIONAL: THERE IS NO VB
 (PROTECTED) BUILDING PER CH 6 AND TABLE 601. THE
 BUILDING CAN HAVE A FIRE SPRINKLER SYSTEM WHICH WILL
 MAKE IT A SPRINKLER BUILDING.
  
 7) SHEET 2 OF 4 ADA RAMP DETAIL SHOWS A 5? LANDING
 AT THE BOTTOM OF THE RAMP. FBC 11-4.8.4 (2) THE BOTTOM
 OF EACH RAMP SHALL NOT LESS THAN 72 INCHES OF STRAIGHT
 AND LEVEL CLEARANCE. THE PLANS SHOW 60 INCHES.
  
 8) 106.3.3* PRODUCT APPROVALS- 2004. THOSE PRODUCTS
 THAT ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. PROVIDE TWO SETS OF PRODUCT
 APPROVALS FOR (A) DOORS (B) WINDOWS (C) ROOF SYSTEM
 METAL AND BUILT-UP ROOF (D) STRUCTURAL CONNECTORS (E)
 FIXED LOUVERS (F) ROOF SCUTTLE (SEE ATTACHED
 INFORMATION). PROVIDE THE SPEC SHEETS FOR THE ?CORIAN?
 SOLID SURFACE SHEETS FOR THE BATHROOMS. SHEET A-5 AND
 A-6 MAKE REFERENCE TO SPRAY ON INSULATION; PROVIDE THE
 SPEC SHEETS SHOWING HOW THE R-19 VALUE WILL BE ACHIEVED
 WITH THE SPRAY ON INSULATION. THE PRODUCT APPROVAL FOR
 THE FLAT ROOM SHALL INDICATE THE FOLLOWING
 INFORMATION.
 1)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY:
 MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / AREA OF
 EACH ROOF TYPE
  
 2)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 IN ADDITION TO THE EVALUATION REPORT SUBMITTED,
 FAC9B72.WWW.FLORIDABUILDING.ORG
  
 3)FOR THE FLAT DECK, SELECT THE APPROVED ASSEMBLY
 YOU ARE USING.ALSO INDICATE WHICH FASTENER IF THE
 OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS.
  
 4)FOR THE FLAT DECK, SPECIFY THE ENHANCED FASTENING
 FOR CORNER AND PERIMETER ZONES.
  
 5)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING.
  
 6)SEE PRODUCT LIMITATION #7.CALCULATIONS PREPARED
 BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
  
  
 9)SHEET A-1 INDICATE THE TYPE OF WALL SEPARATING THE
 MAIN ELECTRICAL ROOM #111 AND THE SHOWER #110. THE
 DIMENSIONS FOR THE SHOWER CONTROLS SHALL BE INDICATED
 ON THE DETAIL DRAWING OF THE SHOWER SHEET A2 DETAIL ?
 SEE FBC 11-4.21.4 AND 11-4.21.5
  
 11)FBC 1802.6.PROVIDE THE ENGINEER SOIL REPORT IN
 ACCORDANCE WITH THIS SECTION OF THE CODE SHOWING THE
 REQUIREMENTS OF 1-9.
  
 12)SHEET A1 ROOM #112 THE KITCHEN, IS THIS A
 COMMERCIAL KITCHEN AND WILL GOODS BE SOLD FROM THIS
 KITCHEN? ADDITIONAL INFORMATION REQUIRED.
  
 13)1209.2 INDICATE THE ATTIC ACCESS ON THE PLANS. AN
 OPENING NOT LESS THAN 20 INCHES BY 30 INCHES SHALL BE
 PROVIDED TO ANY ATTIC AREA HAVING A CLEAR HEIGHT OF
 OVER 30 INCHES.
  
 14)FBC 1203.2ENCLOSED ATTICS AND ENCLOSED RAFTER
 SPACES FORMED WHERE CEILINGS ARE APPLIED DIRECTLYTO
 THE UNDER SIDE SHALL HAVE CROSS VENTILATION. PROVIDE
 THE NECESSARY INFORMATION MEETING THE REQUIREMENTS OF
 THIS SECTION. SHEET A-6 HAS LITTLE INFORMATION ON THE
 SCREEN VENT STRIP. THE STATEMENT REFERS TO A DETAIL BUT
 DOES NOT SAY WHICH PAGE THE DETAIL IS ON.
  
 14)1503.3.6 PROTECTION AGAINST DECAY & TERMITES.
 CONDENSATE LINES & ROOF DOWN SPOUTS SHALL DISCHARGE AT
 LEAST 1 FT. AWAY FROM THE STRUCTURE SIDEWALL, WHETHER
 BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR SPLASH
 BLOCKS. SHEET A-5 DETAIL #3 REFERS TO THE MEP SHEETS
 FOR ADDITIONAL INFORMATION WHICH CANNOT BE FOUND. SHOW
 ON THE DRAWINGS HOW THE DOWNSPOUTS WILL DISCHARGE THE
 WATER AWAY FROM THE BUILDING.
  
 15)SHEET A-3 SCUPPER DETAIL. INDICATE ON THE DETAIL
 DRAWING THE DISTANCE FROM THE FINISH ROOF TO THE BOTTOM
 OF THE OVERFLOW SCUPPER. OVERFLOW SCUPPERS SHALL BE
 PLACED IN WALLS OR PARAPETS NOT LESS THAN 2 INCHES NOR
 MORE THAN 4 INCHES ABOVE THE FINISHED ROOF COVERING.
 FBC 1503.4.3.
  
 16)2210.3 TRUSSES. THE DESIGN, QUALITY ASSURANCE,
 INSTALLATION AND TESTING OF COLD-FORMED STEEL TRUSSES
 SHALL BE IN ACCORDANCE WITH THE STANDARD FOR
 COLD-FORMED STEEL FRAMING?TRUSSES , AMERICAN IRON AND
 STEEL INSTITUTE, SUBJECT TO THE LIMITATIONS THEREIN.
 THE ENGINEER OF RECORD SHALL REVIEW AND APPROVE ALL
 SHOP DRAWINGS INCLUDING THE METAL TRUSSES PRIOR TO
 SUBMITTAL.
  
 17)SHEET A-6 INDICATES SPRAYING FIREPROOFING ON THE
 BEANS AND COLUMNS, WHAT WILL BE THE FIRE RATING AND
 THICKNESS OF THE FIREPROOFING TO ACHIEVE THE RATING?
  
 18)NOTE: 1013.2 AN EXIT ACCESS SHALL NOT PASS THROUGH
 A ROOM THAN CAN BE LOCKED TO PREVENT EGRESS. INDICATE
 THE TYPE OF LOCKS FOR THE EACH DOOR LOCATED IN THE PATH
 OF EGRESS TRAVEL. THIS INFORMATION CAN BE SHOWN ON THE
 DOOR SCHEDULE.
  
 19)SHEET A-3 PROVIDE A DETAIL SHOWING HOW THE FOAM
 CAP WILL BE FASTENS TO THE EXTERIOR OF THE BUILDING.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]