| 2008-08-12 15:00:00 | ** DENIED PLANS.** |
| | |
| | ** PLANS ARE COMING BACK FOR OTHER CORRECTIONS. |
| | |
| | |
| | 1) NOTE: PLANS/RISER NEED TO BE LABELED WITH ALL NEW |
| | SIGNAGE FOR DISCONNECTING MEANS OF NORMAL AND EMERGENCY |
| | POWER. |
| | 230.2E, 702.8 |
| | |
| | 2) NOTE: PLANS CALL FOR A SEPARATELY DERIVED GENERATOR |
| | YET THE SPECS/MANUFACTURES CUT SHEETS/ BILL OF |
| | MATERIALS INDICATES TRANSFER SWITCH AS 3-POLE. IT WAS |
| | NOTED BY ENGINEER OF RECORD HOWEVER NO NEW SPECS WERE |
| | SUBMITTED. |
| | PLEASE SEE SHEET IN REAR OF SUBMITTAL PACKAGE WHICH |
| | STATES THE ISOLATORS ARE N/A. (NOT APPLICABLE). PLEASE |
| | SEE NFPA-110 CHAPTER 7. |
| | |
| | 3) NOTE: PLEASE SEE E.01 AS THE 2002 NFPA-70 (NEC) IS |
| | QUOTED. THIS CAN BE REDLINED WITHOUT CHANGING SHEET. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |