| 2008-06-20 16:09:07 | ** DENIEDREVIEW ** |
| | |
| | |
| | 1) NOTE: |
| | |
| | 2) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS |
| | FOR THE NEW PROPOSED TRANSFER SWITCH EQUIPMENT. 110.3, |
| | 90.7 AS PROPOSED SYSTEMS AND ATS DOES NOT SHOW THESE AS |
| | FOUR UNITS A FULL LIST OF COMMENTS CAN NOT BE GIVEN. |
| | PLEASE SEE 250.50,250.32, 250.20 ETC PLEASE COMPLETE |
| | RISER SHOWING BONDING ETC FOR SDS. |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE NEW PROPOSED GENERATORS. 110.3,90.7 |
| | PLEASE SEE COMMENTS FROM OTHER TRADES FOR INFORMATION |
| | REQUIRED FOR THE PRIME MOVER OF THE GENERATOR. |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 4) NOTE: PLEASE SEE THE RISER AS THIS IS MISSING THE |
| | REQUIRED EQUIPMENT GROUNDING CONDUCTORS FROM THE |
| | GENERATOR TO THE BUILDING. 250.32 |
| | |
| | 5) NOTE: PLEASE PROVIDE VOLTAGE DROP CALCULATIONS PER |
| | 13-413.1ABC.1, .1.1 AND .1.2 |
| | |
| | 6) NOTE: PLEASE SUBMIT SHOW THE SIZES OF THE PANELS, |
| | CONDUITS AND CONDUCTORS FROM ATS DEVICES TO EACH PANEL |
| | H1, H2, H3, H4.L |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |