| 2008-08-08 10:42:05 | PLUMBING PLAN REVIEW: |
| | DENIED **2ND TIME: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE |
| | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW |
| | COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW |
| | COMMENTS. |
| | NOTE: THERE WAS NO COMMENT RESPONSE FROM THE |
| | DESIGNER. |
| | |
| | 1. SHEET 2, PLUMBING HAS TWO DIFFERENT VENT SIZES |
| | BEING INDICATED FOR THE POOL MAIN DRAIN, ONE AS BEING |
| | 1" AND THE OTHER BEING 1-1/2", ALSO THE SPA MAIN DRAIN |
| | VENT PIPING IS BEING INDICATED AS 1-1/2", HOWEVER THE |
| | "ENTRAPMENT AVOIDANCE VENT PIPE ANALYSIS - MAXIMUM |
| | LENGTH" SHEET IS ONLY INDICATING A VENT PIPE TABLE FOR |
| | 1" PIPE. PLEASE CORRELATE AND CORRECT RESUBMITTED |
| | SHEETS WITH VENT PIPE SIZES. PER (W.P.B. AS AMENDED) |
| | SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | **PREVIOUS COMMENT HAS NOT BEEN ADDRESSED. THE |
| | RESUBMITTED PLANS ARE INDICATING AN 1-1/2" VENT, |
| | HOWEVER THE ENTRAPMENT AVOIDANCE VENT PIPE |
| | ANALISIS-MAXIMUM LENGTH DETAIL IS FOR A 1" VENT PIPE. |
| | AS REQUESTED IN THE FIRST PLAN REVIEW PLEASE CORRELATE |
| | ALL SHEETS TO REFLECT THE SAME VENT PIPE SIZE. PER |
| | (W.P.B. AS AMENDED) SECTION 106.1.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS AND FBC-2004 RESIDENTIAL CHAPTER |
| | 41, SECTION R4101.6 ENGINEERING DESIGN. |
| | |
| | 2. "OK" COMMENT ADDRESSED |
| | |
| | 3. "OK" COMMENT ADDRESSED. |
| | |
| | **THE FOLLOWING IS A NEW COMMENT** |
| | |
| | 4. SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR |
| | TIMES THE FEE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |