| Date |
Text |
| 2008-06-05 11:58:39 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET P-1.0 PLUMBING FLOOR PLAN, SANITARY AND WATER |
| | RISER DIAGRAMS: CLEARLY IDENTIFY ALL FIXTURES AS TWO |
| | ARE NOT IDENTIFIED ON THE PLUMBING FLOOR PLAN AND ONE |
| | IS NOT IDENTIFIED ON THE SANITARY AND WATER RISER |
| | DIAGRAMS IN KITCHEN #109. PER FBC-2004 PLUMBING SECTION |
| | 601.1 SCOPE AND SECTION 701.1 SCOPE. |
| | |
| | 2. SHEET P-1.0 WATER RISER DIAGRAM: CLEARLY IDENTIFY |
| | WHAT IS BEING INSTALLED AT EACH FIXTURE FOR WATER |
| | HAMMER. SHEET P-2.0 GENERAL PLUMBING NOTES #17 STATES |
| | "CONTRACTOR SHALL PROVIDE MAINTENANCE FREE MECHANICAL |
| | SHOCK ARRESTORS AT ALL FIXTURES WITH QUICK CLOSING |
| | VALVES", HOWEVER THE FIXTURES INDICATED IN THE WATER |
| | RISER DIAGRAM ARE NOT QUICK CLOSING. AIR CHAMBERS ARE |
| | NOT ACCEPABLE UNLESS THEY ARE PER "STANDARD PDI-WH 201, |
| | A RECHARGABLE TYPE OF AIR CHAMBER"(DETAIL REQUIRED). |
| | PER FBC- 2004 PLUMBING SECTION 604.9 WATER HAMMER. |
| | |
| | 3. SHEET A-2.01 DETAIL #3: CLEARLY INDICATE THE KNEE |
| | CLEARANCE COMPLIANT WITH FBC-2004 CHAPTER 11 SECTION |
| | 11-4.24.3 (27" HIGH, 30" WIDE, AND 19" DEEP SHALL BE |
| | PROVIDED UNDERNEATH SINKS. |
| | |
| | 4. SHEET 1A-1.01 THIRD FLOOR PLAN: CLEARLY INDICATE |
| | THE CLEAR FLOOR SPACE FOR THE SINK IN KITCHEN #109 AND |
| | AND SINK ACROSS FROM ROOM #105 COMPLIANT WITH FBC-2004 |
| | CHAPTER 11 SECTION 11-4.24.5 (30" X 48" AND SHALL |
| | EXTEND A MAXIMUM OF 19" UNDERNEATH THE SINK). |
| | |
| | 5. SHEET P-2.0 PLUMBING FIXTURE CONNECTION SCHEDULE: |
| | FIXTURE P-4 DISCRIPTION IS BEING INDICATED AS A SERVICE |
| | SINK WITH A 2" WASTE. ISN'T THIS A 6-1/2" DEEP |
| | STAINLESS STEEL SINK WITH A 1-1/2" WASTE. PLEASE |
| | CLARIFY THIS ON THE RESUBMITTAL. PER FBC-2004 PLUMBING |
| | SECTION 401.1 SCOPE. |
| | |
| | 6. SHEET A-2.01 DETAIL #2 ADA FOUNTAIN: PER |
| | 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS |
| | PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN |
| | WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS |
| | IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE |
| | TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS |
| | CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR |
| | BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED |
| | ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR SUCH AS A |
| | CUP HOLDER). |
| | |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |
| | |