| 2009-02-19 07:47:52 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. AS THIS IS A THRESHOLD BUILDING, PLEASE INCLUDE THE |
| | STATEMENT REQUIRED BY FBC*109.3.6.4.4 AND |
| | FS553.79(7)(D). |
| | |
| | 2. INCORRECT ASCE REFERENCE WAS PROVIDED ON THE |
| | DECORATIVE BAHAMA SHUTTER CALCULATIONS, FBC35. PLEASE |
| | EITHER REVISE OR PROVIDE A LETTER ADDRESSING THIS |
| | ISSUE. THIS CAN BE A PROVISO ITEM (AT CONTRACTOR'S |
| | RISK). |
| | |
| | 3. PLEASE NOTE THAT THE PRODUCT APPROVALS FOR THE METAL |
| | DOORS (SINGLE AND DOUBLE) DO NOT PROVIDE WATER |
| | INFILTRATION. THIS IS INFORMATIONAL ONLY. |
| | |
| | 4. THE DOUBLE DOOR PRODUCT APPROVAL SUBMITTED COMPLIES |
| | WITH PRESSURES FOR ZONE 4 ONLY. THIS REVISION WILL BE |
| | ISSUED WITH THE PROVISO THAT PRODUCT APPROVALS ARE |
| | REQUIRED FOR DOUBLE DOORS WHICH MEET THE DP REQUIREMENT |
| | OF +61.63/-80.23. |
| | |
| | 5. SHEET S02, ONE SET, HAS NOT BEEN SEALED. |
| | |
| | IF POSSIBLE, PLEASE HAVE THE EOR CONTACT ME TO MAKE AN |
| | APPOINTMENT TO RESOLVE ISSUES #1 AND #5. ONCE THESE |
| | STATUTORY REQUIREMENTS ARE ADDRESSED, OTHER ITEM(S) CAN |
| | BE PROVISO ITEMS. THE SHEETS ARE STAMPED PENDING |
| | RESOLUTION OF #1 AND #5. |
| | |
| | 6. THE RUSKIN (LOUVER) PRODUCT APPROVAL IS TO BE |
| | APPROVED BY DESIGNER OF RECORD FBC*106. |
| | |