| Plan Review Notes For Permit 08050665 |
| Permit Number |
08050665 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-06-03 13:23:56 | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS | | | AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} 240.24(B) OCCUPANCY EACH OCCUPANT SHALL HAVE READY | | | ACCESS TO ALL OVERCURRENT DEVICES PROTECTING THE | | | CONDUCTORS SUPPLYING THAT OCCUPANCY.INDICATE COMPLIANCE | | | WITH THIS ARTICLE | | | | | | 2} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN | | | PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF | | | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE | | | EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE | | | PLAN. | | | | | | 3} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS | | | DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES | | | FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3 | | | FBC AS AMENDED. | | | | | | 4} THE ARCHITECTURAL FIRM MUST DISPLAY THE CERTIFICATE | | | OF AUTHORIZATION ON THE TITLE BLOCK PER 481.221 (8). | | | | | | 5} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8 | | | (2003), AND CIRCUITED PER 700.12 NEC (F)(4). INDICATE | | | SAME ON PLANS. | | | | | | PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE | | | SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | |
|