Plan Review Notes
Plan Review Notes For Permit 08050665
Permit Number 08050665
Review Stop E
Sequence Number 1
Notes
Date Text
2008-06-03 13:23:56THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 240.24(B) OCCUPANCY EACH OCCUPANT SHALL HAVE READY
 ACCESS TO ALL OVERCURRENT DEVICES PROTECTING THE
 CONDUCTORS SUPPLYING THAT OCCUPANCY.INDICATE COMPLIANCE
 WITH THIS ARTICLE
  
 2} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN
 PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE
 EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE
 PLAN.
  
 3} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3
 FBC AS AMENDED.
  
 4} THE ARCHITECTURAL FIRM MUST DISPLAY THE CERTIFICATE
 OF AUTHORIZATION ON THE TITLE BLOCK PER 481.221 (8).
  
 5} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8
 (2003), AND CIRCUITED PER 700.12 NEC (F)(4). INDICATE
 SAME ON PLANS.
  
 PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  