| Date |
Text |
| 2008-06-27 16:26:36 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET A-0.0 GROUP B OCCUPANCY LOAD OF 51: PLANS ARE |
| | NOT COMPLIANT PER FBC- PLUMBING TABLE 403.1 MINIMUM |
| | NUMBER OF REQUIRED PLUMBING FIXTURES. PROPOSED FLOOR |
| | PLAN ON SHEET A-2.1 INDICATES ONE (1) WATER CLOSET AND |
| | ONE (1) LAVATORY, HOWEVER THREE (3) WATER CLOSETS ARE |
| | REQUIRED, THREE (3) LAVATORIES ARE REQUIRED, AND ONE |
| | (1) DRINKING FOUNTAIN IS REQUIRED. |
| | |
| | 2. SHEET A-1.1 DEMO PLANS ARE INCOMPLETE PER FIELD |
| | INSPECTION THERE IS AN EXISTING MOP SINK AND SINK |
| | ROUGHED IN THAT ARE NOT INDICATED ON THE DEMO PLANS. |
| | ALL FIXTURES THAT ARE TO BE DEMOED SHALL BE INDICATED |
| | ON THE PLANS. PER FBC- PLUMBING 401.1 AND 701.1 SCOPE |
| | AND PER FBC- PLUMBING, SECTION 704.5 DEAD ENDS: IN THE |
| | INSTALLATION OR REMOVAL OF ANY PART OF A DRAINAGE |
| | SYSTEM, DEAD ENDS SHALL BE PROHIBITED. A PLUMBING |
| | PERMIT IS REQUIRED AND AN INSPECTION IS REQUIRED OF |
| | PLUMBING DEMO WORK PRIOR TO COVERING DEMO WORK WITH |
| | FINNISH WALLS, CIELINGS, OR POURED CONCRETE SLABS. |
| | (PLEASE ADD TO NOTES) |
| | |
| | 3. SHEET A-2.1 HANDICAPPED BATHROOM PLAN & ELEVATIONS |
| | DETAIL (B) H.C. TOILET ROOM ELEVATION: THE LAVATORY |
| | NEEDS TO INDICATE COMPLIANCE WITH 11-4.19.2 PROVIDE A |
| | CLEARANCE OF AT LEAST 29 INCHES ABOVE FINNISH FLOOR TO |
| | THE BOTTOM OF THE APRON. KNEE AND TOE CLEARANCES SHALL |
| | COMPLY WITH FIGURE 31. ALSO 11-4.19.5 FAUCETS NEEDS TO |
| | BE INDICATED. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |