| 2008-05-22 16:51:04 | ****CORRECTIONS**** |
| | ROBERT MCDOUGAL, BUILDING PLANS EXAMINER |
| | 561-805-6714 [email protected] |
| | |
| | 2004 FLORIDA BUILDING CODE & |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE 2004 FBC |
| | ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| | |
| | ____1.)EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER |
| | BARRIER REQUIRED FS553.844(5)(A). PROVIDE |
| | INFORMATION (PRODUCT APPROVAL OR SPECIFICATIONS) TO |
| | SHOW HOW YOU WILL COMPLY WITH THIS REQUIREMENT. |
| | INFORMATION IS AVAILABLE AT WWW.BOAF.NET, HURRICANE |
| | MITIGATION. |
| | |
| | ____2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| | INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY; |
| | MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF |
| | EACH ROOF TYPE |
| | |
| | ____3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED IN ADDITION TO THE EVALUATION REPORT |
| | SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG |
| | |
| | __X__4.)FOR THE FLAT ROOF, SELECT THE APPROVED |
| | ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER |
| | YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE |
| | LIMITATIONS. SEE PAGES 32 AND 33 OF THE NOA FOR |
| | NON-INSULATED WOOD DECKS AND FASTENING OPTIONS. |
| | |
| | __X__5.)FOR THE FLAT ROOF, SPECIFY THE ENHANCED |
| | FASTENING FOR CORNER AND PERIMETER ZONES.THIS IS TO |
| | BE EITHER WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED |
| | ON LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB |
| | SHEET). THE FASTENER SPACINGS SPECIFIED ON SECTION D |
| | ARE NOT ADEQUATE. |
| | |
| | ____ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH |
| | METHOD OF ATTACHMENT YOU ARE USING.IF YOU SELECT FOAM |
| | ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72. |
| | |
| | ____ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS |
| | PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| | CONSULTANT REQUIRED FOR ENHANCED FASTENING. |
| | |
| | |
| | PROVISO ? MECHANICAL EQUIPMENT TO COMPLY WITH FBC |
| | EB511, FBC1509.7. |
| | |
| | |
| | DOUBLE UNDERLAYMENT 1507.2.8 |
| | DOUBLE UNDERLAYMENT TILE FBC R905.3.3.1, 2 ? / 12 UP TO |
| | 4/12 |