2008-09-10 09:13:01GAS PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND
 WITH THE PREVIOUS GAS PLAN REVIEW COMMENTS AS WELL AS
 TE DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY.
 NEW COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS
 REVIEW COMMENTS.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS. PER FBC-
 FUEL GAS CODE SECTION 401.1 SCOPE.
 NOTE: THERE WERE NO CORRESPONDING LENGTHS FOR THE CUT
 SECTIONS OF PIPE INDICATED ON GAS ISOMETRIC DRAWING.
  
 **NO COMMENT RESPONSE FROM THE DESIGNER AND THE COMMENT
 WAS NOT ADDRESSED. THE RESUBMITTED GAS ISOMETRIC STILL
 DOES NOT INDICATE CORRESPONDING LENGTHS TO ALL CUT
 SECTIONS OF PIPE. THE ONLY CUT SECTIONS OF PIPE WITH
 CORRESPONDING LENGTHS BEING INDICATED IS THE
 UNDERGROUND PE PIPING. WHAT ARE THE CORRESPONDING
 LENGTHS TO THE ABOVE GROUND PIPING? PER SECTION 401.1
 SCOPE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. PER FBC- FUEL GAS
 CODE SECTION 401.1 SCOPE.
 NOTE: THE ONLY PIPING MATERIAL INDICATED WAS FOR THE
 UNDERGROUND PIPING. WHAT IS THE PIPING MATERIAL FOR THE
 ABOVE GROUND?
  
 **NO COMMENT RESPONSE FROM THE DESIGNER AND THE COMMENT
 WAS PARTIALLY ADDRESSED. WHAT IS THE TYPE AND SIZE OF
 THE PIPING MATERIAL OF THE ABOVE GROUND PIPING AT THE
 METER LOCATION? PER SECTION 401.1 SCOPE.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: REFERENCE COMMENT #1 AND COMPLY.
  
 **NO COMMENT RESPONSE FROM THE DESIGNER AND COMMENT WAS
 NOT ADDRESSED. PLEASE REFERENCE COMMENT #1 AND COMPLY.
  
 4. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER,
 THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA
 STATUTES 481 AND 471 RESPECTIVELY.
 NOTE: SUBMITTED GAS ISOMETRIC HAS NO SIGNATURES.
  
 **NO COMMENT RESPONSE FROM THE DESIGNER AND COMMENT WAS
 NOT ADDRESSED. THE RESUBMITTED GAS ISOMETRIC DRAWINGS
 DO NOT HAVE ANYONE TAKING RESPONSIBILITY FOR THEM. THE
 PRINTED NAME WITH THE ORIGNAL SIGNATURE OF THE PERSON
 TAKING RESPOSIBILITY FOR THE ISOMETRIC IS STILL
 REQUIRED. PER (W.P.B. AS AMENDED) SECTION 106.3.4.3.
  
 **THE FOLLOWING ARE NEW COMMENTS DUE TO THE RESUBMITTAL
 PACKAGE AND NEW GAS ISOMETRIC.
  
 5. THERE ARE TWO DIFFERENT GENERATOR MANUFACTURE
 SPECIFICATION SHEETS MAKE AND MODEL NUMBERS WITH
 DIFFERENT BTU LOAD CAPACITIES IN THE RESUBMITTAL.
 PLEASE KNOW THAT THIS IS CONFUSING AND UNACCEPTABLE. A
 GENERAC MODEL QT030 WITH A BTU CAPACITY OF 525,000 AND
 A GAURDIAN MODEL #5219 WITH A 412,000 BTU CAPACITY IS
 IN THE RESUBMITTAL. PLEASE CORRELATE THE RESUBMITTAL
 WITH ONLY ONE MAKE AND MODEL OF GENERATOR MANUFACTURE
 SPECIFICATIONS. PER FBC-2004 FUEL GAS SECTION 401.1
 SCOPE.
  
 6. SUBMIT TWO COPIES OF MANUFACTURE SHEETS FOR THE MP
 REGULATORS (2ND STAGE REGULATORS) TO VERIFY COMPLIANCE
 WITH STANDARDS NFPA 54, NFPA 58, AND THE FBC-2004 FUEL
 GAS CODE SEC 402.2. THE MANUFACTURE SHEETS SHALL
 CLEARLY INDICATE THE MP REGULATORS MAKE, MODEL NUMBER,
 BTU LOAD CAPACITY, AND A LISTING FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY (LISTING EXAMPLES= AGA,
 CSA, UL).
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  