| 2008-09-15 15:03:42 | |
| | ** DENIED ** |
| | |
| | 1) NOTE: PERMIT APPLICATION FOR PRIME CONTRACTOR NEEDS |
| | TO BE REVISED FOR INSTALLATION OF THE GENERATOR. FS |
| | 527.02 |
| | |
| | 2) NOTE: PERMIT APPLICATION STATES 35KW GENERATOR |
| | HOWEVER PLANS AND SUPPORTING DOCUMENTS STATE 30KW. |
| | PLEASE COORDINATE APPLICATION AND ALL DOCUMENTS. |
| | NEC 2005 |
| | FBC 106.1.1, 106.5 FOR COORDINATION AND CLARITY OF |
| | PLANS AND RECORD PLANS. |
| | |
| | 3) NOTE: PLEASE KNOW AT THIS TIME THE RISER AND SCOPE |
| | OF WORK IS CONFUSING TO THIS REVIEWER. THE PLANS/RISER |
| | CONTAINS NOTES WHICH CALLS FOR A 35KW 3-PHASE GENERATOR |
| | AND ALSO CALLS FOR A SINGLE-PHASE 30KW GENERATOR. |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |