Plan Review Notes
Plan Review Notes For Permit 08050638
Permit Number 08050638
Review Stop B
Sequence Number 2
Notes
Date Text
2008-09-12 10:26:45BUILDING PLAN REVIEW
 PERMIT: 08050638
 ADD: 901 45TH ST
 CONT: JT ELECTRIC
 TEL: (561) 723-5956
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SEPT.12,2008
 2ND REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B): PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
 SITE PLAN FOR QUANTUM HOUSE PLEASE PROVIDE
 IDENTIFICATION AS TO WHO DESIGNED SITE PLAN NAME AND
 TELEPHONE NUMBER. 10106.1.1.
  
 1C) COMPLIED.
  
 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
 HILLMAN ENGINEERING DOES NOT PROVIDE UPDATES UNDER THE
 2004 FBC 2007 SUPPLEMENTS.
  
 2) COMPLIED.
  
 3) HILLMAN ENGINEERING PLANS ARE COPIES NOT SIGNED NOR
 SEALED. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 4) HILLMAN ENGINEERING PLAN INDICATES THE USE OF A
 FEATHER LITE GENERATOR PAD PLEASE PROVIDE DOCUMENTATION
 FOR USE FOR A GENERATOR. ADDITIONAL INFORMATION
 REQUIRED.106.1.2.
 4A) PLANS DO NOT INDICATE IF THE PAD AND GENERATOR ARE
 TO BE SHOP MOUNTED PAD OR FIELD MOUNTED PAD.
  
 4B) PLANS ARE NOT HIGHLIGHTED AS TO WHICH PAD WILL BE
 INSTALLED, NOTE KEEP IN MIND THE REQUIRED 4" EDGE
 DISTANCE IN DETERMINING PAD SIZE.
  
 5) COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.