Plan Review Notes
Plan Review Notes For Permit 08050638
Permit Number 08050638
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-06-30 16:29:33*****DENIED*****
  
  
  
 1.PROVIDE A SITE PLAN SHOWING THE LOCATION OF
 GENERATOR WITH RESPECT TO PROPERTY LINES, PUBLIC WAYS,
 AND BUILDING(S) ON THE PROPERTY.
  
 2.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY RESPONSE TO THE SAID PROPERTY OR THE
 VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE
 LANES, ETC) .
  
 3.PLEASE INDICATE THE USAGE OF THE STATIONARY
 GENERATOR AS FOR EMERGENCY USE OR STANDBY POWER.
  
 4.THE GENERATOR SHALL BE INSTALLED IN ACCORDANCE WITH
 NFPA 110, 2002 EDITION.
  
 5.DEPENDING UPON LOCATION OF THE EQUIPMENT,
 SAFEGUARDS AGAINST MECHANICAL DAMAGE MAY BE REQUIRED
 AND SHALL BE ILLUSTRATED.
  
 6.EQUIPMENT USING GAS AND RELATED GAS PIPING SHALL BE
 ACCORDANCE WITH NFPA 54.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW