Plan Review Notes
Plan Review Notes For Permit 08050638
Permit Number 08050638
Review Stop E
Sequence Number 1
Notes
Date Text
2008-06-18 13:40:32** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE FS 527.02 AS THE PRIME CONTRACTOR
 SHALL CONTAIN STATE REQUIRED LICENSING TO SELL,
 INSTALLED GAS AND NATURAL GAS APPLIANCES.
 PLEASE SUPPLY THE LICENSING UNDER THE ELECTRICAL
 INFORMATION AS THE PRIME CONTRACTOR IS LISTED AS AN
 ELECTRICAL CONTRACTOR WHICH MAY NOT APPLY FOR PERMIT,
 SELLOR INSTALL THESE TYPES OF GENERATORS UNLESS
 LICENSED.
 PLEASE KNOW THE GAS CONTRACTOR MAY BE THE PRIME
 CONTRACTOR IF NOT LICENSED.
 THIS HAS BEEN CONFIRMED WITH THE LICENSING BOARD AND ON
 RECENTPHONE AUDITS FROM A STATE LEVEL DEPARTMENT OF
 AGRICULTURE.
  
 2) NOTE: PLEASE LIST THE TYPE OF SYSTEM THIS GENERATOR
 WILL FEED. IS THIS EMERGENCY, LEGALLY REQUIRED OR
 STRICTLY OPTIONAL STAND-BY?
 IF OTHER THAN OPTIONAL STAND-BY, ON-SITE FUEL IS
 REQUIRED.
 700.12.B3, 701.11B3
  
 3) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE PROPOSED ATS.
 110.3, 90.7
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 4) NOTE: PLEASE SUBMIT MINIMUM QUALITY OF PLANS WHICH
 DOES NOT CONTAIN HAND WRITTEN PLANS IN PEN AND
 WHITE-OUT.
 FBC 106.1
  
 5) NOTE: PLEASE SUBMIT THE SPECS/MANUFACTURES CUT
 SHEETS FOR THE GENERATOR WHICH COORDINATES WITH PLANS.
 PLEAS SEE SPECS SUBMITTED IN PACKAGE FOR 45KW
 GENERATOR.
 SPECS NEED TO STATE MINIMUM CLEARANCES AROUND UNIT.
 PLEASE SEE MINIMUM REQUIREMENTS FOR ZONING WAS A WALL
 MAY BE REQUIRED. SHRUBS MAY NOT BE THE ONLY
 REQUIREMENT.
 THE SITE PLANS NEED MORE DETAILS FOR LOCATION, SETBACKS
 AND DIMENSIONS OF ALL EQUIPMENT.
 PLEASE SHOW ALL LOCATIONS OF ELECTRICAL EQUIPMENT AS
 PROPOSED.
 THIS WILL AFFECT ENTIRE SET OF PLANS.
 110.26, 225.31-225.39 ETC WHICH CAN NOT BE VERIFIED AT
 THIS TIME.
  
 6) NOTE: PLEASE SEE THE APPLIED VALUE NEEDS TO BE
 ADJUSTED AS THE SCOPE OF ENTIRE PROJECT WILL INCREASE
 DUE TO WALL ETC.
 FBC 108.3
  
 7) NOTE: PLEASE SEE CHECKLIST AND SEVERAL DOCUMENTS
 SUBMITTED ARE ACTUALLY FROM PALM BEACH COUNTY WHEN
 PROJECT IS LOCATION IN THE CITY OF WEST PALM BEACH.
  
 8) NOTE: PLEASE SEE RISER SHOWS THE NEW EMERGENCY PANEL
 AS 125AMP RATED WITH A 150AMP BREAKER FROM THE
 GENERATOR FEEDING THIS PANEL WHICH CONTAINS 125AMP
 RATED LUGS ETC.
 ALSO SHOWS #1 WHICH ARE NOT RATED FOR 150AMPS. MAY NOT
 USE 310.15B6 AND MUST USE 310.16 FOR SIZING
 CONDUCTORS.
  
 ** AS SEVERAL ITEMS ARE NOT SHOWN AT THIS TIME, REVIEW
 FOR COMPLETE CODE COMPLIANCE CAN NOT BE DONE.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved