| Notes |
| Date |
Text |
| 2008-05-22 16:54:16 | RESIDENTIAL (R3)SHUTTERS, BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1- ACCORDING TO KEY PLAN SUBMITTED OPENING #2 IS THE | | | EGRESS OPENING. CLARIFY HOW COMPLYING WITH SEC.R310.4 | | | OF 2004 FLORIDA RESIDENTIAL CODE, WHERE AT LEAST ONE | | | MEANS OF ESCAPE IS REQUIRED WHEN SHUTTERS ARE | | | INSTALLED. | | | | | | 2- CLARIFY WHY TWO DIFFERENT SCHEDULES WHERE SUBMITTED | | | WITH DIFFERENT DESIGN PRESSURES AND BUILDING EXPOSURE. | | | ANCHOR SPACING FOR -62PSF DESIGN PRESSURES NEEDS TO BE | | | REVISED. SEE REDLINEDINSTALLATION SCHEDULE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561) 805-6712 |
|