2008-08-28 13:45:50PLANS ROUTED TO LUIS M FOR PROCESSING
2008-08-28 13:45:17 
 ** REDLINED PLANS **
  
  
  
 1) NOTE:THE FOLLOWING ITEMS WERE REDLINED AND/OR
 NOTED ON PLANS.
  
 **ALL REVISIONS SHALL BE SUBMITTED, REVIEWED, STAMPED
 AND ON-SITE FOR ELECTRICAL INSPECTOR BEFORE ROUGH
 ELECTRICAL INSPECTION.
 **ALL LOW VOLTAGE SYSTEMS INCLUDING FIRE ALARM SYSTEM
 ARE REQUIRED TO BE UNDER SEPARATE PERMITS.
 **ALL NEW LIGHTING CONTROLS SHALL MEET
 13-415.1.ABC.1.1,.1.2 AND .1.3 FOR MINIMUM PRESCRIPTIVE
 REQUIREMENTS.
 **ALL HORN AND STROBE DEVICES SHALL MEET FBC CHAPTER
 11. PLANS NOTE NFPA-72 WHICH IS ALSO CORRECT HOWEVER
 SOME REQUIREMENTS IN THE FBC ARE MORE RESTRICTIVE.
 11-4.28.1,.2 AND .3.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  