| Plan Review Notes For Permit 08050632 |
| Permit Number |
08050632 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-08-28 13:45:50 | PLANS ROUTED TO LUIS M FOR PROCESSING | | 2008-08-28 13:45:17 | | | | ** REDLINED PLANS ** | | | | | | | | | | | | 1) NOTE:THE FOLLOWING ITEMS WERE REDLINED AND/OR | | | NOTED ON PLANS. | | | | | | **ALL REVISIONS SHALL BE SUBMITTED, REVIEWED, STAMPED | | | AND ON-SITE FOR ELECTRICAL INSPECTOR BEFORE ROUGH | | | ELECTRICAL INSPECTION. | | | **ALL LOW VOLTAGE SYSTEMS INCLUDING FIRE ALARM SYSTEM | | | ARE REQUIRED TO BE UNDER SEPARATE PERMITS. | | | **ALL NEW LIGHTING CONTROLS SHALL MEET | | | 13-415.1.ABC.1.1,.1.2 AND .1.3 FOR MINIMUM PRESCRIPTIVE | | | REQUIREMENTS. | | | **ALL HORN AND STROBE DEVICES SHALL MEET FBC CHAPTER | | | 11. PLANS NOTE NFPA-72 WHICH IS ALSO CORRECT HOWEVER | | | SOME REQUIREMENTS IN THE FBC ARE MORE RESTRICTIVE. | | | 11-4.28.1,.2 AND .3. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|