Plan Review Notes
Plan Review Notes For Permit 08050632
Permit Number 08050632
Review Stop E
Sequence Number 2
Notes
Date Text
2008-08-07 15:12:55 
 **DENIED 2ND REVIEW**
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE:PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER FOR ALL FIRMS LISTED ON TITLE
 BLOCKS. PLEASE SEE THAT THE LICENSE ON ARCHITECTURAL
 SHEETS FOR FIRM TEWES DESIGN GROUP INC IS BEING SHOWN
 ON THE STATE WEBSITE AS NULL AND VOID.
 PLEASE PROVIDE UP TO DATE ACCURATE LICENSE NUMBER FOR
 SAID FIRM. PLANS MAY BE HANDED OVER TO LEGAL COUNSEL
 FOR THE FLORIDA BOARD OF ARCHITECTS AS NO RELEVANT
 LICENSE COULD BE FOUND AS REQUIRED PER FAC 61G1-16.004
 AND FS 481.219.
  
 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 AS
 PLANS WERE NOT REVISED TO SHOW AND INDICATE THE
 REQUIRED DEVICES FOR AUTOMATE LIGHTING CONTROLS. IN
 FACT THE PLANS CONTAIN A NOTE QUOTING THE CODE. THE
 CODE IN GENERAL OR SPECIFIC CODE REQUIREMENT SHALL NOT
 BE QUOTED IN LIEU OF MINIMUM DESIGN.
 ONE EXAMPLE ALONE WOULD BE THE FACT THE SYMBOL LEGEND
 STILL SHOWS STANDARDS SINGLE POLE DEVICES WHICH ARE NOT
 ACCEPTABLE TO MEET THE MINIMUM CODE.
  
 3) NOTE: PLEASE SUBMIT COMPLETE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1, .1.2. THE
 PLANS CONTAIN SOME INFORMATION AND SEEM TO BE ON THE
 RIGHT TRACK HOWEVER AS THE FIXTURES ON PLANS AND A
 REQUIRED FIXTURE LEGEND IS NOT COMPLETE WITH ALL
 INFORMATION ON ALL FIXTURES; REVIEW FOR MINIMUM CODE
 COMPLIANCE CAN NOT BE DONE.
 PLEASE COMPLETE INFORMATION ON ALL FIXTURES.
  
 4) NOTE: PLEASE BE SURE THE NEW CIRCUITS ON PANEL
 SCHEDULES ARE SPECIFIC TO ROOMS AND AREAS IN WHICH THEY
 FEED.
 408.4
  
 5) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE AS SOME OF THE CODE
 SECTIONS FROM THE PREVIOUS REVIEW ARE BEING REPEATED
 FOR THE SECOND REVIEW. THIS IS ONLY A NOTICE GIVEN AT
 THIS TIME.
 AS THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION
 THIS SECTION OF THE STATUTES AS NOTED WOULD APPLY TO
 ANY COMMENTS ON THE REVIEW AFTER NEXT. PLEASE BE SURE
 TO ADDRESS COMMENTS.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]