| 2008-06-16 11:39:58 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL SHEETS WITH ARCHITECTURAL TITLE BLOCKS. THE |
| | BUSINESS LICENSE NUMBER, (CERTIFICATE OF |
| | AUTHORIZATION), IS REQUIRED ON EACH SHEET. THE STATE OF |
| | FLORIDA DEPT OF PROFESSIONAL REGULATION, (DBPR), |
| | INDICATES THE BUSINESS NUMBER IS NULL AND VOID SINCE |
| | 2/28/2005. THIS NUMBER IS REQUIRED PER FAC |
| | 61G1-16.004(1) & FS 481.219. (SEE ATTACHED SHEET). |
| | |
| | 2. SHTS A-1.1 & ME-5 IN THE REMOVAL OF ANY PART OF A |
| | DRAINAGE SYSTEM, DEAD SHALL BE PROHIBITED. SECTION |
| | 704.5. ALL DEMO'D/CAPPED PIPING SHALL NOT BE COVERED |
| | PRIOR TO FIELD INSPECTORS INSPECTION &APPROVAL. |
| | |
| | 3. SHT A-2 ELEVATION "A" SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | A. 11-4.24.3 KNEE CLEARANCE |
| | B. 11-4.24.4 SINK DEPTH |
| | C. 11-4.24.5 CLEAR FLOOR SPACE. (FORWARD APPROACH |
| | REQD. CABINET DOORS NOT APPROVED). |
| | D. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | E. 11-4.24.7 FAUCETS |
| | |
| | 4. ALL ME SHEETS. THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER IS REQUIRED ON EACH SHEET. FAC 61G15-23.002(2) & |
| | FS 471.025. (SEE ATTACHED SHEET). |
| | |
| | 5. SHT ME-1 SHOWS SINKS THAT WERE DELETED ON THE |
| | ARCHITECTURAL FLOOR PLAN. PLEASE CORRELATE. SECTION |
| | 106.1.1. |
| | |
| | 6. SHT ME-5 THE WATER HAMMER ARRESTOR SHALL BE LOCATED |
| | NEAR THE FIXTURE, (REF),IN AN "EFFECTIVE RANGE", NOT |
| | IN THE CEILING AS SHOWN. PDI-WH 201. SECTION 604.9. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |