Plan Review Notes
Plan Review Notes For Permit 08050632
Permit Number 08050632
Review Stop M
Sequence Number 1
Notes
Date Text
2008-06-20 09:35:03REVIEW #: 1ST **PLAN CHECK ONLY**
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE LEVEL OF ALTERATION IS NOT DECLARED ON PLANS.
 THE DESIGN PROFESSIONALMUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION IN ACCORDANCE WITH
 FBCEB 301.5.
  
 2. PROVIDE OUTSIDE AIR CALCULATIONS INCLUDING OCCUPANT
 LOAD, VENTILATION REQUIRED AND VENTILATION PROVIDED IN
 ACCORDANCE WITH FBCM TABLE 403.3. SEE ALSO FBCEB
 609.1.
  