| Plan Review Notes For Permit 08050632 |
| Permit Number |
08050632 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-06-30 13:14:52 | *****DENIED***** | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCDTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER | | | ACCESS TO / EGRESS FROM THE OTHER FLOORS OF THE | | | BUILDING. | | | | | | 4.ON SHEET A-1, REFERENCE THE 2004 EDITION OF THE | | | FLORIDA FIRE PREVENTION (NOT 2005)AND THE 2003 | | | EDITION OF NFPA 101 (NOT 2004) . | | | | | | 5.ON SHEET A-2, NO LEGEND FOR THE DOOR TYPES 1 AND 2 | | | NOTED. | | | | | | 6.ON SHEET ME-3, STROBE DEVICE V6-2-7 SHOWN AS | | | RELOCATED(R) BUT LISTED AS EXISTING (E);STROBE | | | DEVICE V6-2-10 SHOWN AS (E) BUT LISTED AS (R);STROBE | | | DEVICE V6-2-11 SHOWN AS (E) BUT LISTED AS (R) . | | | | | | 7.PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR | | | THIS SCOPE OF WORK LOCATION. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | | EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|