2008-06-30 13:14:52*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCDTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 ACCESS TO / EGRESS FROM THE OTHER FLOORS OF THE
 BUILDING.
  
 4.ON SHEET A-1, REFERENCE THE 2004 EDITION OF THE
 FLORIDA FIRE PREVENTION (NOT 2005)AND THE 2003
 EDITION OF NFPA 101 (NOT 2004) .
  
 5.ON SHEET A-2, NO LEGEND FOR THE DOOR TYPES 1 AND 2
 NOTED.
  
 6.ON SHEET ME-3, STROBE DEVICE V6-2-7 SHOWN AS
 RELOCATED(R) BUT LISTED AS EXISTING (E);STROBE
 DEVICE V6-2-10 SHOWN AS (E) BUT LISTED AS (R);STROBE
 DEVICE V6-2-11 SHOWN AS (E) BUT LISTED AS (R) .
  
 7.PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR
 THIS SCOPE OF WORK LOCATION.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  