Plan Review Notes
Plan Review Notes For Permit 08050632
Permit Number 08050632
Review Stop E
Sequence Number 1
Notes
Date Text
2008-06-19 14:23:10** DENIEDREVIEW **
  
  
 1) NOTE:PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN
 REVIEW AND NOT FOR PERMIT. PLEASE KNOW EVEN ONCE PLANS
 ARE FOUND TO BE CODE COMPLIANT THE REVIEW WILL STILL
 REMAINED IN A FAILED STATUS UNTIL PERMIT APPLICATION IS
 MADE. LICENSING AND SEVERAL OTHER ITEMS ARE VERIFIED AT
 TIME OF APPLICATION.
  
 2) NOTE: PLEASE SEE FAC 61G1-16.004 AND FLORIDA
 STATUTES 481.219 AS THE TITLE BLOCKS ARE MISSING THE
 REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER.
  
 3) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON ELECTRICAL PLANS AT A MINIMUM.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101 (PLANS NOTE A 2004 NFPA-101 WHICH DOES
 NOT EXIST)
 2002 NFPA-72
  
 4) NOTE: PLEASE SEE FAC 61G15-23.002 AND FS 471.023 AS
 THE MEP TITLE BLOCKS ARE MISSING THE REQUIRED
 CERTIFICATE OF AUTHORIZATION NUMBER.
 THIS IS REQUIRED ON ALL SHEETS FOR ALL TRADES WHETHER
 OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 5) NOTE: PLEASE SEE THE SEAL WHICH IS IN USE BY THE
 ENGINEER IS NO LONGER VALID IN THE STATE OF FLORIDA.
 PLEASE SEE RULING DATED FEB 2004 IN WHICH ALL SEALS FOR
 ENGINEERS WERE REQUIRED TO GO THE WORDING OF LICENSE
 HOWEVER AN EXTENSION WAS GRANTED HOWEVER ONLY TO THE
 DATE OF DECEMBER 31ST, 2005. SEAL HAS NOT BEEN VALID TO
 BE USED IN THE STATE OF FLORIDA SINCE JANUARY 1ST,
 2006.
 FAC61G15-23.001
  
 6) NOTE: PLEASE SEE PLANS ARE VERY CONGESTED AND NOT
 EASILY READ. PLEASE SEE FBC 106.1.3 AS THE PLANS SHALL
 BE A MINIMUM OF 1/8 TH INCH SCALE.
 PLANS MENTIONS THE SCALE IS 1/8TH INCH HOWEVER BASED ON
 CEILING GRID FOR EXAMPLE WHICH SHOWS 2FT BY 2FT TILES,
 THESE DO NOT COORDINATE.
 PLEASE ADJUST AND SUBMIT.
  
 7) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND PLACE
 NOTES ON PLANS ACCORDINGLY.
  
 8) NOTE: PLEASE SEE 13-415.1.ABC.1.1,.1.2 AND .1.3 FOR
 NEW LIGHTING CONTROLS BEING INSTALLED.
  
 9) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.1.1,.1.2 FOR
 MINIMUM LIGHTING PERFORMANCE CALCULATIONS COMPLIANCE.
  
 10) NOTE: PLEASE SEE 240.21, 408.36 AS THE PANEL ON THE
 SECONDARY SIDE OF THE TRANSFORMER SHALL CONTAIN OVER
 CURRENT PROTECTION.
 RISER INDICATES EXISTING MAIN CIRCUIT BREAKER YET THE
 PANEL 6L INDICATES THIS PANEL AND MAIN LUG ONLY.
  
 11) NOTE: PLEASE SEE THE MINIMUM LEVELS FOR HORN
 STROBES SHALL MEET FBC 11-4.28.1, .2 AND .3(4). THE
 LEVELS STATED ON PLANS ARE NOT CLEAR FOR ALL.
 PLEASE SEE IT IS UNCLEAR WHAT THE 15 BEFORE IS.
 IF THIS IS A HORN LEVEL, THE LEVEL IS TOO LOW.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS WHICH ARE NOT
 YET SHOWN FOR CODE COMPLIANCE, THERE MAY VERY WELL BE
 NEW COMMENTS ON THE FOLLOWING REVIEW.
  
 ** ONE SET OF PLANS ARE BEING RETAINED.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]