| Date |
Text |
| 2008-06-19 14:23:10 | ** DENIEDREVIEW ** |
| | |
| | |
| | 1) NOTE:PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN |
| | REVIEW AND NOT FOR PERMIT. PLEASE KNOW EVEN ONCE PLANS |
| | ARE FOUND TO BE CODE COMPLIANT THE REVIEW WILL STILL |
| | REMAINED IN A FAILED STATUS UNTIL PERMIT APPLICATION IS |
| | MADE. LICENSING AND SEVERAL OTHER ITEMS ARE VERIFIED AT |
| | TIME OF APPLICATION. |
| | |
| | 2) NOTE: PLEASE SEE FAC 61G1-16.004 AND FLORIDA |
| | STATUTES 481.219 AS THE TITLE BLOCKS ARE MISSING THE |
| | REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER. |
| | |
| | 3) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED |
| | ON ELECTRICAL PLANS AT A MINIMUM. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 (PLANS NOTE A 2004 NFPA-101 WHICH DOES |
| | NOT EXIST) |
| | 2002 NFPA-72 |
| | |
| | 4) NOTE: PLEASE SEE FAC 61G15-23.002 AND FS 471.023 AS |
| | THE MEP TITLE BLOCKS ARE MISSING THE REQUIRED |
| | CERTIFICATE OF AUTHORIZATION NUMBER. |
| | THIS IS REQUIRED ON ALL SHEETS FOR ALL TRADES WHETHER |
| | OR NOT COMMENT IS MADE BY OTHER TRADES. |
| | |
| | 5) NOTE: PLEASE SEE THE SEAL WHICH IS IN USE BY THE |
| | ENGINEER IS NO LONGER VALID IN THE STATE OF FLORIDA. |
| | PLEASE SEE RULING DATED FEB 2004 IN WHICH ALL SEALS FOR |
| | ENGINEERS WERE REQUIRED TO GO THE WORDING OF LICENSE |
| | HOWEVER AN EXTENSION WAS GRANTED HOWEVER ONLY TO THE |
| | DATE OF DECEMBER 31ST, 2005. SEAL HAS NOT BEEN VALID TO |
| | BE USED IN THE STATE OF FLORIDA SINCE JANUARY 1ST, |
| | 2006. |
| | FAC61G15-23.001 |
| | |
| | 6) NOTE: PLEASE SEE PLANS ARE VERY CONGESTED AND NOT |
| | EASILY READ. PLEASE SEE FBC 106.1.3 AS THE PLANS SHALL |
| | BE A MINIMUM OF 1/8 TH INCH SCALE. |
| | PLANS MENTIONS THE SCALE IS 1/8TH INCH HOWEVER BASED ON |
| | CEILING GRID FOR EXAMPLE WHICH SHOWS 2FT BY 2FT TILES, |
| | THESE DO NOT COORDINATE. |
| | PLEASE ADJUST AND SUBMIT. |
| | |
| | 7) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND PLACE |
| | NOTES ON PLANS ACCORDINGLY. |
| | |
| | 8) NOTE: PLEASE SEE 13-415.1.ABC.1.1,.1.2 AND .1.3 FOR |
| | NEW LIGHTING CONTROLS BEING INSTALLED. |
| | |
| | 9) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.1.1,.1.2 FOR |
| | MINIMUM LIGHTING PERFORMANCE CALCULATIONS COMPLIANCE. |
| | |
| | 10) NOTE: PLEASE SEE 240.21, 408.36 AS THE PANEL ON THE |
| | SECONDARY SIDE OF THE TRANSFORMER SHALL CONTAIN OVER |
| | CURRENT PROTECTION. |
| | RISER INDICATES EXISTING MAIN CIRCUIT BREAKER YET THE |
| | PANEL 6L INDICATES THIS PANEL AND MAIN LUG ONLY. |
| | |
| | 11) NOTE: PLEASE SEE THE MINIMUM LEVELS FOR HORN |
| | STROBES SHALL MEET FBC 11-4.28.1, .2 AND .3(4). THE |
| | LEVELS STATED ON PLANS ARE NOT CLEAR FOR ALL. |
| | PLEASE SEE IT IS UNCLEAR WHAT THE 15 BEFORE IS. |
| | IF THIS IS A HORN LEVEL, THE LEVEL IS TOO LOW. |
| | |
| | ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS WHICH ARE NOT |
| | YET SHOWN FOR CODE COMPLIANCE, THERE MAY VERY WELL BE |
| | NEW COMMENTS ON THE FOLLOWING REVIEW. |
| | |
| | ** ONE SET OF PLANS ARE BEING RETAINED. |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |