| 2008-06-20 11:07:43 | BUILDING PLAN REVIEW |
| | PERMIT: 08050629 |
| | ADD: 777 S. FLAGLER DRIVE SUITE 1500 |
| | CONT: BUTLER CONSTRUCTION |
| | TEL: (561)832-9700 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 6-19-08 |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. |
| | |
| | 4)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| | OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| | THIS CODE. |
| | |
| | 5)THE DOOR SCHEDULE HAS CONFLICTING INFORMATION WHEN |
| | REFERRING TO THE DOOR TYPES EXAMPLE, DOOR #1510; THE |
| | DOOR SCHEDULE INDICATETYPE (C)AS A SOLID WOOD |
| | SINGLE DOOR ACCORDING TO THE DOOR TYPES, HOWEVER THE |
| | MATERIAL IS NOTED AS GLASS ON THE SCHEDULE. PLEASE NOTE |
| | THERE IS NO TYPE (A2) DOOR SHOWN ON SHEET A-1.0, |
| | HOWEVER IT IS INDICATED IN THE DOOR SCHEDULE. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED. 106.1.1. |
| | |
| | 6)INDICATE HOW THE METAL TRACK OR ANY MATERIAL WILL |
| | BE FASTENED TO THE STRUCTURE ABOVE. THE DETAIL SHEETS |
| | SHALL STATE THE TYPE OF FASTENERS TO BE USED. THERE IS |
| | NO INDICATION AS TO WHAT TYPE OF FASTENERS WILL BE |
| | USED. |
| | 7)FBC 603. DUE TO THE FACT THAT THIS IS A TYPE I |
| | BUILDING THE FURRING AND BACKING MATERIALS SHALL BE |
| | FIRE-RETARDANT-WOOD WHICH IS NOT STATED ON SOME OF THE |
| | DETAIL SHEETS. INTERIOR FINISH MATERIALS ARE REQUIRED |
| | TO BE APPLIED DIRECTLY TO EXPOSED SURFACES OF |
| | STRUCTURAL ELEMENTS OR TO FURRING STRIPS NOT EXCEEDING |
| | 1.75 INCHES ATTACHED TO SUCH SURFACES. FBC 803.4.1. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |
| 2008-06-19 15:50:45 | REVIEW IN PROGRESS |