| 2008-06-20 16:36:48 | *****DENIED***** |
| | |
| | |
| | 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 02.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| | SHALL BE REMOVED FORM THE SITE AT THE END OF EACH SHIFT |
| | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 03.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE |
| | EMERGENCY RESPONSE TO THE SAID PROPERTY OR THE VICINITY |
| | THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES, ETC.) |
| | . |
| | |
| | 04.ON SHEET A-1, WHAT IS THE DOOR NUMBER IS SCHEDULED |
| | FOR THE ROOM CONTAINING THE AIR HANDLER UNIT (A.H.U.) |
| | ? |
| | |
| | 05.ON SHEET A-2, ROOM DOOR 215 LOCATED BETWEEN THE |
| | ELEVATOR AND THE FOYER IS LISTED AS LIVING ROOM. PLEASE |
| | EXPLAIN. |
| | |
| | 06.ON SHEET A-2, ROOM DOOR 212 IS LISTED IN THE DOOR |
| | SCHEDULE AS BATHROOM. |
| | |
| | 07.ON SHEET E-1 & E-2, REFERENCES ARE MADE TO SMOKE |
| | DETECTORS BEING USED IN THE DWELLING UNITS.PLEASE BE |
| | ADVISED THAT MOKE DETECTORS (SD) ARE TIED INTO A |
| | BUILDING'S FIRE ALARM SYSTEM, WHEREAS SMOKE ALARMS |
| | SOUND ONLY WITHIN AN INDIVIDUAL DWELLING UNIT AND SHALL |
| | NOT ACTUATE THE BUILDING FIRE ALARM SYSTEM. |
| | |
| | 08.PROVIDE PRESCRIPTIVE STRENGHTS FOR THE STAIR |
| | HANDRAILS/GUARDRAILS. |
| | |
| | 09.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 10.30.1.2.2- NO DWELLING UNIT OF A RESIDENTIAL |
| | OCCUPANCY SHALL HAVE ITS SOLE MEANS OF EGRESS PASS |
| | THROUGH ANY NONRESIDENTIAL OCCUPANCY IN THE SAME |
| | BUILDING. |
| | |
| | 11.30.1.2.3- THE SEPARATION OF THE DWELLING UNITS |
| | OF THE RESIDENTIAL OCCUPANCY AND EXITS FROM THE |
| | NONRESIDENTIAL OCCUPANCY SHALL BE BY CONSTRUCTION |
| | HAVING A FIRE RESISTAIVE RATING OF NOT LESS THAN 1 |
| | HOUR. |
| | |
| | 12.30.3.3.2- SPECIFY THE INTERIOR FINISH FOR THE |
| | EXIT ENCLOSURE, LOBBIES AND CORRIDORS, AND OTHER SPACES |
| | IN TERMS OF CLASS A, CLASS B, OR CLASS C. |
| | |
| | 13.30.3.5.11 - SHOW THE LOCATION OF THE 2A10 BC RATED |
| | FIRE EXTINGUISHERS WHICH SATIFISFY THE 75' TRAVEL |
| | DISTANCE. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET |
| | EACH COMMENT WAS ADDRESSED. |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |