| 2008-06-19 12:34:43 | ** DENIEDREVIEW ** |
| | |
| | |
| | 1) NOTE:PLEASE SEE THAT PLANS AND DOCUMENTS NEEDED TO |
| | BE SUBMITTED ARE NOT COMPLETE AT THIS TIME. THERE MAY |
| | VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH |
| | CAN NOT BE MADE AT THIS TIME DUE TO LACK OF INFORMATION |
| | AND CODE COMPLIANCE. |
| | |
| | 2) NOTE: PLEASE SEE ATTACHED PRINT OUT FROM THE |
| | DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION.AT |
| | THE TIME OF THIS REVIEW THE PRINT OUT INDICATES THE |
| | ARCHITECT OF RECORD AS SIGNED, DATED AND SEALED ON |
| | PLANS LICENSE WAS SUSPENDED IN JULY 2007. THIS LICENSE |
| | IS NOT CURRENT AS SHOWN BY THE STATE AND PLANS MAY NOT |
| | BE SIGNED, DATED AND SEALED BY THIS ARCHITECT AS |
| | SHOWN. |
| | ** CONTACT HAS BEEN MADE TO THE BOARD OF ARCHITECTS |
| | LEGAL COUNSEL TO VERIFY THE STATE WEBSITE INFORMATION |
| | AS SHOWN IS ACCURATE. |
| | |
| | 3) NOTE: PLEASE BE SURE TO COMPLETE ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED PANEL |
| | SCHEDULES. |
| | PLEASE SEE MOST OF DEVICES WHICH DO NOT INDICATE ANY |
| | CIRCUITS AND MANY CIRCUITS WHICH DO NOT CORRELATE WITH |
| | THE SUBMITTED SCHEDULES. THERE ARE SEVERAL CODES WHICH |
| | MINIMUM CIRCUITING CAN NOT BE VERIFIED FOR CODE |
| | COMPLIANCE AT THIS TIME. |
| | FBC ADMIN SECTION 106.3.5.1.2, 106.5.4 |
| | NEC 408.4, 240.4, 310.16, 210.52, 210.11 ETC |
| | |
| | 4) NOTE: PLEASE BE SURE PLANS REFERENCE THE CURRENT |
| | CODES IN EFFECT AS LISTED. |
| | NFPA-101 2003, NFPA-72 2002, NFPA-70 2005, AND 2004 FBC |
| | W/ 2007 REVISIONS. |
| | |
| | 5) NOTE: PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS |
| | FOR ALL AREAS WHICH ARE APPLICABLE FOR USE AND |
| | OCCUPANCY. PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 |
| | AND .1.3 FOR LIGHTING PERFORMANCE CALCULATIONS. PLEASE |
| | SEE 13-400.3.A, 13-400.3.B, 13-400.3.C, 13-101.3. AS |
| | THE MINIMUM REQUIRED CALCULATIONS WERE NOT SUBMITTED |
| | MINIMUM CODE COMPLIANCE HAS NOT BEEN MET OR VERIFIED. |
| | |
| | 6) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AS THE FOLLOWING |
| | WORDING IS REQUIRED TO BE ON PLANS. |
| | CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT WITHIN 30 |
| | DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD |
| | DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED |
| | TO THE BUILDING OWNER, INCLUDING:13-413.1.ABC.2.2 |
| | MANUALS. |
| | CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT AN OPERATING |
| | MANUAL AND MAINTENANCE MANUAL BE PROVIDED TO THE |
| | BUILDING OWNER. THE MANUALS SHALL INCLUDE, AT A |
| | MINIMUM, THE FOLLOWING: |
| | 1. SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED |
| | OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING |
| | MAINTENANCE. |
| | 2. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH |
| | PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED |
| | ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY |
| | IDENTIFIED. |
| | 3. NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED |
| | SERVICE AGENCY. |
| | NOTE: ENFORCEMENT AGENCIES SHOULD ONLY CHECK TO BE SURE |
| | THAT THE CONSTRUCTION DOCUMENTS REQUIRE THIS |
| | INFORMATION TO BE TRANSMITTED TO THE OWNER AND SHOULD |
| | NOT EXPECT COPIES OF ANY OF THE MATERIALS. |
| | SOME TEXT ABOVE WAS TAKEN DIRECTLY FROM THE FBC FOR |
| | EASE OF CORRECT WORDING REQUIRED ON PLANS. |
| | |
| | 7) NOTE: PLEASE SEE THE RISER SUBMITTED IS NOT COMPLETE |
| | AT THIS TIME. PLEASE SEE NO MAINS, NO OVER CURRENT |
| | PROTECTION FOR PANELS, MAINS ETC WERE SUBMITTED OR |
| | SHOWN. |
| | PLEASE SUBMIT A COMPLETE RISER DIAGRAM MEETING MINIMUM |
| | CODE COMPLIANCE FOR SERVICES. 230.70,230.71,230.72, |
| | 215.5, 310.16, 240.4 ETC |
| | ** |
| | 8) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING |
| | CONDUCTOR TO EACH PANEL. |
| | 250.110,250.122, 250.24 ETC. |
| | |
| | 9) NOTE: PLEASE SEE GROUNDING ELECTRODE SYSTEM MENTIONS |
| | TO ATTACH TO FOOTER STEEL? PLEASE KNOW IN AN EXISTING |
| | BUILDING, IT IS NOT REQUIRED AND IS NOT RECOMMENDED DUE |
| | TO THE STRUCTURAL INTEGRITY OF THE EXISTING |
| | STEEL/FOOTER. |
| | PLEASE KNOW HOWEVER THIS IS PERMITTED AND IF SHOWN ON |
| | RISER, IT WILL BE REQUIRED. |
| | 250.50 |
| | |
| | 10) NOTE: PLEASE SEE 250.66 FOR SIZING OF GROUNDING |
| | ELECTRODE CONDUCTOR AS THIS IS CURRENTLY SHOWN AS A |
| | "6/0"? PLEASE KNOW THIS IS NOT A RECOGNIZED STANDARD IN |
| | THE NATIONAL ELECTRICAL CODE OR THE AMERICAN WIRE GAUGE |
| | STANDARD. PLEASE ADJUST AS NEED BASED ON SERVICE |
| | ENTRANCE CONDUCTORS WHICH WILL BE BASED ON LOAD |
| | CALCULATIONS.PLEASE BE SURE TO SEE COMMENTS BELOW FOR |
| | MINIMUM SERVICE ENTRANCE CONDUCTORS TO VERIFY. |
| | |
| | 11) NOTE: PLEASE SEE NOTE WITH RESPECT TO LOAD |
| | CALCULATIONS. AS THE SUBMITTED CALCULATIONS DO NOT |
| | MINIMUM CODE COMPLIANCE THE SIZE OF THE EXISTING |
| | SERVICE ENTRANCE CONDUCTORS AS SHOWN ON RISER CAN NOT |
| | BE VERIFIED. |
| | |
| | 10) NOTE: PLEASE SUBMIT AIC RATINGS FOR ALL NEW SERVICE |
| | EQUIPMENT BEING INSTALLED. PLEASE SEE 110.9 AS MAINS, |
| | BREAKERS AND ALL SERVICE EQUIPMENT IS REQUIRED TO RATED |
| | FOR THE AVAILABLE FAULT CURRENT. |
| | PLEASE SEE NOTE #20 AS LISTED ON E-2 WHICH MENTIONS TO |
| | USE FUSES HOWEVER AS NO INFORMATION IS SHOWN ON RISER |
| | FOR ANY MAINS, SERVICE EQUIPMENT ETC THESE CAN NOT BE |
| | VERIFIED. |
| | |
| | 12) NOTE: PLEASE SHOW LOAD CALCULATIONS MEETING THE |
| | 2005 NEC> PLEASE SEE THE CODE SECTIONS REFLECTED ON |
| | PLANS ARE NOT FROM THE 2005 NATIONAL ELECTRICAL CODE. |
| | PLEASE SEE THE COMMERCIAL PORTION OF THE BUILDING |
| | ACTUALLY SHOWS *RESIDENTIAL* LOAD CALCULATIONS. HOW IS |
| | THIS POSSIBLE? WHERE IN THE NEC DOES IT PERMIT |
| | RESIDENTIAL LOAD CALCULATIONS IN COMMERCIAL OFFICE |
| | SPACE? |
| | PLEASE SEE 220.12, 220.14, 220.42, 220.43, ETC. PLEASE |
| | BE SURE TO SHOW ALL CONTINUOUS LOADS AT 125% PER 215.3, |
| | 230.42 ETC. |
| | AS CALCULATIONS ARE NOT COMPLETE AND THERE IS MUCH NEED |
| | FOR COORDINATION PLEASE KNOW NEW COMMENTS MAY ARISE |
| | ONCE THESE ARE RESUBMITTED. |
| | |
| | 13) NOTE: PLEASE SEE COMMON AREAS ON PLANS WILL REQUIRE |
| | SOME SORT OF *HOUSE/COMMON* ARE PANEL. THESE CIRCUITS |
| | IN THESE AREAS MAY NOT BE FED FROM THE APARTMENT UNITS |
| | OR COMMERCIAL TENANT SPACE. |
| | 210.25 ETC. AS MOST OF THE CIRCUITING IS NOT SHOWN MOST |
| | ITEMS CAN NOT BE VERIFIED FOR MINIMUM CODE COMPLIANCE. |
| | |
| | 14) NOTE: PLEASE SHOW ALL PANEL LOCATIONS FOR |
| | VERIFICATION OF CODE COMPLIANCE. |
| | 110.26,240.24 ETC. |
| | FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION |
| | AND COORDINATION. |
| | |
| | 15) NOTE: PLEASE CORRELATE ALL LOAD FOR A/C SYSTEMS, AS |
| | MECHANICAL PLANS INDICATE 10KW UNITS, LOAD |
| | CALCULATIONS |
| | INDICATE BOTH 9KW LOAD AND 5KW LOAD AND PANEL SCHEDULES |
| | INDICATE 5KW HEAT FOR ALL?? |
| | PLEASE ADJUST LOAD CALCULATIONS AND COORDINATE OTHER |
| | COMMENTS. |
| | |
| | 16) NOTE: PLEASE SEE 424.3B WHICH REQUIRES ALL MINIMUM |
| | OVER CURRENT PROTECTION FOR AIR HANDLER UNIT HEAT TO BE |
| | SIZED AT A MINIMUM OF 125%. |
| | PLEASE SEE PANEL SCHEDULES SHOWS 50A, #6 AWG ON 5KW |
| | UNITS. |
| | |
| | 17) NOTE: PLEASE SEE CONDUCTORS SHOWN FOR RANGE/OVENS |
| | WHICH DO NOT SHOW ANY NEUTRAL CONDUCTOR AS REQUIRED PER |
| | 250.140 |
| | |
| | 18) NOTE: PLEASE SEE MISSING MINIMUM DISCONNECTS FOR |
| | ALL AIR CONDITIONING EQUIPMENT. AS NOT ALL EQUIPMENT IS |
| | CURRENTLY SHOWN PLEASE BE SURE TO SEE 440.11 AND 110.26 |
| | AND SHOW LOCATIONS OF ALL REQUIRED DISCONNECTS. |
| | |
| | 19) NOTE: PLEASE SEE MISSING REQUIRED GFI SERVICE |
| | RECEPTACLE FOR OUTSIDE CONDENSING UNITS.210.63, |
| | 210.8A3, 210.8B4. |
| | |
| | 20) NOTE: PLEASE SEE AN ELEVATOR IS SHOWN ON PLANS, |
| | HOWEVER THERE IS NO INDICATION ON ANY PLANS OF THIS |
| | EQUIPMENT OR EQUIPMENT ROOM. |
| | PLEASE SHOW LOCATION OF EQUIPMENT. |
| | PLEASE SEE 620.23, 620.24 FOR MISSING REQUIRED |
| | DEDICATED CIRCUITS. PLEASE SEE SAME SECTIONS AS |
| | RECEPTACLE SHALL BE GFI PROTECTED. |
| | PLEASE SEE 700.16 FOR MISSING BACK UP LIGHT DEPENDING |
| | ON LOCATION OF EQUIPMENT. |
| | |
| | 21) NOTE: PLEASE SEE 13-415.1.ABC.1.4 FOR REQUIRED |
| | CONTROL OF OUTSIDE LIGHT. SOME LIGHTS NOTE TO BE |
| | CIRCUITED TO A TC (ASSUMING TIME CLOCK) HOWEVER PLEASE |
| | SEE CURRENT CODE SECTION GIVEN AS A STANDARD TIME CLOCK |
| | IS NOT ACCEPTABLE. |
| | PLEASE PROVIDE ONE OF TWO ACCEPTABLE METHODS AND |
| | INDICATE ON PLANS. |
| | PLEASE BE SURE TO SEE NOTES ABOVE WITH RESPECT TO |
| | COMMON AREAS WHICH OUTSIDE LIGHTING WOULD BE TO NEW |
| | HOUSE PANEL ETC. |
| | |
| | 22) NOTE: PLEASE SEE THE MISSING REQUIRED DEDICATED |
| | SIGN CIRCUIT AS PER 600.5 |
| | |
| | 23) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR |
| | MINIMUM LIGHTING LEVELS UNDER THE 2003 NFPA-101 LIFE |
| | SAFETY CODE FOR EGRESS PATHS AND STAIRS. |
| | PLEASE SEE 7.8.1.3, 7.9.2.2. |
| | PLEASE KNOW AS THESE ARE COMMON AREAS, CONTROLS AND |
| | CIRCUITING NEED TO BE ADJUSTED ACCORDING. |
| | |
| | 24) NOTE: PLEASE SEE PLANS SHOW SD FOR SMOKE DETECTORS |
| | AS DEFINED IN NFAP-72. IF THESE ARE TRULY SMOKE |
| | DETECTORS WHICH ONLY DETECT AND DO NOT SOUND AN ALARM |
| | PLEASE SUBMIT THE COMPLETE FIRE ALARM SYSTEM INCLUDING |
| | HORNS, FIRE ALARM PANEL ETC. |
| | PLEASE SEE THE COMMON AREAS MAY NOT HAVE THE |
| | RESIDENTIAL UNITS SMOKE ALARMS DEVICES WIRED INLINE OR |
| | SAME CIRCUITS. |
| | PLEASE ADJUST. |
| | PLEASE SEE THE DEFINITIONS FOR SMOKE ALARMS AND SMOKE |
| | DETECTORS AND ADJUST DESIGN ACCORDINGLY. |
| | |
| | 25) NOTE: PLEASE PROVIDE A FIXTURE LEGEND/SCHEDULE AND |
| | CORRELATE WITH THE PLANS. PLEASE BE SURE THE FIXTURE |
| | LEGEND IS COMPLETE FOR ALL COMMON AREAS AND OFFICE |
| | AREAS. PLEASE INCLUDE AREAS FOR RESIDENTIAL ALSO WITH |
| | RESPECT TO THE RECESSED LIGHTING FIXTURES. |
| | 13-415.2.ABC.1, 13-415.2 FOR COMMERCIAL, |
| | 13-606.1.ABC.1.2.4 FOR RESIDENTIAL. |
| | |
| | 26)NOTE: PLEASE BE SURE TO SEE 700.12F FOR CIRCUITING |
| | OF REQUIRED EMERGENCY AND EXIT LIGHT FIXTURES. |
| | |
| | 27) NOTE: PLEASE SEE 210.8A2WHICH REQUIRES A;; |
| | RECEPTACLES IN BATHROOMS TO BE SHOWN AS GFI/GFI |
| | PROTECTED. SOME ARE AND SOME ARE NTO. |
| | |
| | 28) NOTE: PLEASE SEE 210.52D, 210.11C3 FOR MISSING |
| | REQUIRED DEDICATES BATH CIRCUITS. MUST BE 20AMP AND #12 |
| | MINIMUM. |
| | |
| | 29) NOTE: PLEASE SEE NFPA-72 11.8.3 FOR LOCATIONS AND |
| | TYPES OF SMOKE DETECTION DEVICES WITHIN 20FT OF COOKING |
| | APPLIANCES. |
| | PLEASE ALSO SEE NOTE ON PLANS WHICH MENTIONS SMOKE |
| | DETECTORS ARE TO BE WIRED AHEAD OF THE SWITCHES ON |
| | EITHER BATH OR KITCHEN LIGHTING CIRCUIT, PLEASE SEE |
| | THIS IS OK, HOWEVER ARC FAULT PROTECTION WILL THEN BE |
| | REQUIRED FOR THOSE LIGHTING CIRCUITS. |
| | 210.12 NEC |
| | |
| | 31) NOTE: PLEASE LIST ALL THE REQUIRED ARC FAULT |
| | PROTECTED CIRCUITS AS REQUIRED PER 2005 NEC 210.12B. |
| | PLEASE SEE COMMENTS ABOVE AS THE CIRCUITS SHALL BE |
| | SPECIFIC AND AS OTHER COMMENTS HAVE AFFECTED DEDICATED |
| | CIRCUITS PER NOTES PLEASE BE SURE TO COORDINATE. |
| | |
| | 32) NOTE: PLEASE BE SURE TO SEE 220.52, 210.52B1 FOR |
| | DINING ROOM/AREA CIRCUITING. |
| | |
| | 33) NOTE: PLEASE SEE MANY CIRCUITS ON PLANS MENTIONS |
| | *GENERAL LIGHTS* AND GENERAL RECEPTACLES*. |
| | PLEASE SEE 408.4 AS ALL CIRCUITING SHALL BE SPECIFIC TO |
| | ROOMS AND AREAS IN WHICH THEY FEED. |
| | FBC 106.1.2, 106.3.5.1.2, 106.3.5.4 |
| | |
| | 34) NOTE: PLEASE BE SURE TO LABEL APARTMENT UNITS ON |
| | ELECTRICAL PLANS. *A*, *B* ETC |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | REVIEW FOR CIRCUITING WILL NEED TO BE DONE. |
| | |
| | 35) NOTE: PLEASE SEE 422.30, 422.31 FOR MISSING |
| | DISCONNECTS FOR WATER HEATERS. |
| | |
| | 36) NOTE: PLEASE SEE 210.52 FOR MISSING RECEPTACLES. |
| | (REDLINED ON ONE SET OF PLANS. |
| | |
| | 37) NOTE: PLEASE SEE PLANS FOR OFFICE WHICH SHOWS A |
| | CIRCUIT FOR WHAT IS LISTED ON PANEL SCHEDULE AS BEING A |
| | MICROWAVE # 14, HOWEVER NO DEVICE OR LOCATION IS SHOWN |
| | ON PLANS. |
| | |
| | 38) NOTE: PLEASE SEE SWITCHES WHICH ARE SHOWN WIRED TO |
| | A 3-WAY SYSTEM ON STAIRS, HOWEVER DO NOT INDICATE BEING |
| | S3. |
| | PLEASE SEE MINIMUM LIGHTING CONTROLS FOR EGRESS |
| | LIGHTING IN FBC CHAPTER 10 AND NFPA-1017.8 |
| | PLEASE SEE OTHER AREAS OF PLANS IN WHICH 3-WAY |
| | SWITCHING IS SHOWN HOWEVER THE 3-WAY SWITCH IS ONLY |
| | SHOWN AT ONE END WHEN IT MUST BE AT MORE THAN ONE |
| | LOCATION. |
| | |
| | 39) NOTE: PLEASE SEE THE ELECTRICAL PLANS AS THE PLANS |
| | ARE MISSING 210.63, 210.70 COMPLIANCE FOR AIR HANDLING |
| | UNITS. |
| | AS THESE WERE NOT SHOWN ON ELECTRICAL PLANS THE |
| | MECHANICAL PLANS WERE LOOKED AT HOWEVER THIS BECAME |
| | MORE CONFUSING AS PACKAGE UNITS AND SPILT SYSTEMS WERE |
| | SHOWN. |
| | IF THESE UNITS ARE PACKAGE UNITS ON ROOF, THEN WHY ARE |
| | THERE CONDENSING UNITS SHOWN ON THE GROUND FLOOR |
| | OUTSIDE LEVEL? |
| | IT IS UNCLEAR WHAT THE DESIGN IS GOING TO BE AS SPILT |
| | SYSTEMS ARE ALSO LISTED ON EQUIPMENT SCHEDULE. PLEASE |
| | COORDINATE ALL AND SEE NOTES ABOVE WITH RESPECT TO |
| | MISSING DISCONNECTS, COORDINATION OF HEAT STRIPS, OVER |
| | CURRENT PROTECTIONS, GFI RECEPTACLES, LIGHTS ETC. |
| | |
| | 40) NOTE: PLEASE SEE MISSING GFI DESIGNATIONS FOR |
| | GARAGE RECEPTACLES. |
| | 210.8A2, 5 |
| | |
| | 41) NOTE: PLEASE SEE MISSING CONTROL FOR EXHAUST FAN ON |
| | FIRST FLOOR BATHROOM. |
| | FBC 106.1.2 |
| | |
| | 42) NOTE: PLEASE SEE ELECTRICAL RISER CLEARLY STATES |
| | THE FEEDERS AS NOTED WILL BE TYPICAL OF *FOUR* (4) YET |
| | THE PLANS ONLY SHOW THREE SPACES, THREE PANELS ETC. |
| | PLEASE CLEAR THIS UP AND COORDINATE. |
| | |
| | 43) NOTE: BASED ON COMMENTS ABOVE ONE SET OF PLANS ARE |
| | BEING RETAINED BY THIS OFFICE. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |