| 2008-05-29 12:19:26 | ** DENIEDREVIEW ** |
| | |
| | 1) NOTE: PLEASE SUBMIT THE RISER DIAGRAM SHOWING THE |
| | FEEDERS AND THE SIZE OF THE OVER CURRENT PROTECTION |
| | FROM THE SERVICE PANEL/EQUIPMENT. |
| | PLEASE KNOW THE BASE HOUSE PLANS WHICH ARE IN FOR |
| | REVIEW BY THIS OFFICE DOES NOT CONTAIN ANY POOL SUB |
| | PANEL, FEED FOR POOL PANEL, BREAKER, LOADS ETC FIGURED |
| | FOR THE NEW SUB PANEL. |
| | PLEASE SUBMIT RISER, LOADS CALCULATIONS FOR ADDED LOADS |
| | ETC. |
| | 220.83, 240.4, 310.16, 225.31-225.39. |
| | |
| | 2) NOTE: PLEASE SEE ZONING COMMENTS AS THIS WILL |
| | DEFINITELY AFFECT THE ELECTRICAL EQUIPMENT, LOCATION |
| | ETC. |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 3) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING |
| | CONDUCTOR FROM SOURCE TO NEW SUB PANEL. |
| | 250.50, 250.32. |
| | |
| | 4) NOTE: PLEASE SHOW THE *AQUA LOGIC* PANEL ON RISER. |
| | WILL THIS UNIT BE CONTROLLING ANY HIGH VOLTAGE |
| | SYSTEMS? |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE KNOW THE WORDING ADDED TO PLANS FOR |
| | INFORMATION REGARDING THE FLORIDA BUILDING COMMISSION |
| | AND ADOPTION OF RULES ETC FOR THE EQUAL POTENTIAL GRID |
| | IS NOT REQUIRED TO BE ON PLANS. ONLY THE DETAIL FOR THE |
| | INSTALLATION NEEDS TO BE ON PLANS. PLEASE SHOW LAYOUT. |
| | 680.26 |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |