| Plan Review Notes For Permit 08050594 |
| Permit Number |
08050594 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-06-18 16:07:16 | | | | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS | | | AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE HEAT | | | PUMPS INTENDED TO BE INSTALLED, BE SURE ELECTRICAL | | | SPEC'S ARE INCLUDED. | | | | | | 2} THE HEAT PUMP LOADS ARE NOT INCLUDED IN THE | | | ELECTRICAL LOAD CALCULATIONS. INCLUDE SAME FOR FEEDER | | | AND PANEL OCP SIZING. ARTICLES 220 AND 215.. | | | | | | 3} INDICATE THE PANEL DESIGNATION, OVERCURRENT | | | PROTECTION AND CONDUCTOR SIZES FOR THE POOL PANEL | | | FEEDERS. | | | | | | 4} THE RECIRCULATING PUMPS LISTED IN THE LOAD | | | CALCULATIONS ARE NOT ON THE ELECTRICAL DIAGRAM, 2 OF | | | 3. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|