| Plan Review Notes For Permit 08050578 |
| Permit Number |
08050578 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-06-10 12:13:23 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) PLEASE SUBMIT A SITE PLAN SHOWING THE PROPERTY | | | LINES, BUILDINGS, AND GENERATOR LOCATION, PER NFPA 37 | | | 4.1.4. | | | | | | 2) PLEASE SUBMIT DETAILED MANUFACTURER'S | | | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE | | | GENERATOR. | | | | | | 3) PLEASE STATE ON PLANS WHAT FUEL TYPE THE GENERATOR | | | IS. | | | | | | 4) IF FUEL TYPE IS OTHER THAN NATURAL GAS SHOW THE | | | LOCATION OF THE FUEL STORAGE TANK AND CAPACITY ON THE | | | SITE PLAN, SEE NFPA 317.9. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|