| 2008-06-09 12:21:27 | DENIED |
| | REFERENCE: FBC-2004 CHAPTER 1 |
| | |
| | 1. MORE INFORMATION REQUIRED. SUBMIT MANUF. |
| | SPECIFICATION AND INSTALLATION INSTRUCTIONS TO |
| | DETERMINE LISTING, CLEARANCES AND INDICATE THE ENERGY |
| | SOURCE FOR THE GENERATORS, (DIESEL, NATURAL GAS, |
| | LP-GAS). SECTION 106.1.2 |
| | |
| | 2. ONLY ELECTRICAL PLANS WERE SUBMITTED. A REVIEW CAN |
| | NOT BE DONE FOR THE GENERATORS WITHOUT MORE |
| | INFORMATION. SITE PLANS WITH SETBACK INFORMATION FROM |
| | THE PROPERTY LINE, OR FLOOR PLAN WITH CLEARANCES FROM |
| | ALL STRUCTURES IS REQUIRED. INFORMATION FOR THE EXHAUST |
| | IS REQUIRED SHOWING ALL OPENINGS TO THE BUILDING AS |
| | WELL AS OVERHANG FROM THE ROOF ETC. REQUIRED. SECTION |
| | 106.1.2. |
| | |
| | 3. WHEN THE REQUIRED INFORMATION IS SUBMITTED, MORE |
| | COMMENTS MAY BE FORTHCOMING. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |