| Plan Review Notes For Permit 08050578 |
| Permit Number |
08050578 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-07-01 14:58:12 | ***DENIED*** | | | | | | 1) ADD NFPA 110, STANDARD FOR EMERGENCY POWER AND | | | STANDBY SYSTEMS TO CODES AND STANDARDS ON SHEET E0.1. | | | | | | 2) CLEARLY IDENTIFY THE FUEL TYPE AND SHOW LOCATION OF | | | FUEL SOURCE. | | | | | | 3) IF APPLICABLE DEPENDING ON TYPE OF FUEL, SHOW | | | BUILDING OPENING LOCATIONS WITH RELATION TO EXHAUST | | | TERMINUS. | | | | | | 4) PLEASE IDENTIFY WHAT BUILDING LIFE SAFETY SYSTEMS | | | AND EQUIPMENT WILL BE CONNECTED TO GENERATORS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|