Plan Review Notes
Plan Review Notes For Permit 08050570
Permit Number 08050570
Review Stop Z
Sequence Number 1
Notes
Date Text
2008-05-28 09:53:46***FAILED***
  
  
 1)PROVIDE BEAR ISLAND ACC (ARCHITECTURAL CONTROL
 COMMITTEE) APPROVAL.
  
 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED
 GENERATOR EQUIPMENT TO ALL PROPERTY LINES.AS PER
 SECTION 94-305(B)(4) OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - GENRES BOX