Plan Review Notes
Plan Review Notes For Permit 08050570
Permit Number 08050570
Review Stop G
Sequence Number 1
Notes
Date Text
2008-06-04 13:32:49GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 NOTE: THE SUBMITTED ISOMETRIC IS ONLY INDICATING THE
 CORRESPONDING LENGTH TO THE UNDERGROUND PE. CLEARLY
 INDICATE THE CORRESPONDING LENGTHS TO ALL CUT SECTIONS
 OF PIPE. WHAT ARE THE ABOVE GROUND CORRESPONDING
 LENGTHS TO THE CUT SECTIONS OF PIPE?
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. PER FBC-2004 FUEL
 GAS SECTION 401.1 SCOPE.
 NOTE: THE ONLY PIPING MATERIAL INDICATED ON THE
 DRAWING IS PE. THE PLANS ARE INDICATING FINAL CONNECT
 PER FBC 411.1, HOWEVER THAT SECTION IS VAUGE. WHAT ARE
 THE ABOVE GROUND PIPING MATERIAL AND SIZES? CLEARLY
 INDICATE ALL PIPING MATERIALS AND SIZES FOR THE
 PROPOSED GENERATOR.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: REFERENCE COMMENT #1.
  
 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: PLEASE SUBMIT THE 2ND STAGE REGULATOR
 MANUFACTURER'S SPECIFICATIONS SHEETS CLEARLY INDICATING
 THE MAKE, MODEL NUMBER, BTU LOAD CAPACITIES, AND A
 LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
  
 5. A GAS PERMIT CAN NOT BE ISSUED UNTIL
 THE GEN/RES PERMIT APPLICATION HAS BEEN
 APPROVED BY ZONING FOR THE GENERATOR LOCATION.
 NOTE: CLEARLY INDICATE THE PROPOSED GENERATORS
 LOCATION FROM PROPERTY LINE AND ADJACENT STRUCTURES.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  