| 2008-05-28 10:35:58 | ** DENIED ** |
| | |
| | 1) NOTE:PLEASE KNOW PER FS 527.02 THE PRIMARY |
| | GENERATOR PERMIT SHALL BE APPLIED FOR UNDER LICENSES AS |
| | REQUIRED. MAY NO LONGER USE THE U-# ASSOCIATED WITH THE |
| | ELECTRICAL CONTRACTOR. THE ELECTRICAL LICENSE NUMBER |
| | STILL MAY BE USED FOR THE ELECTRICAL SUB-PERMIT. THIS |
| | HAS BEEN RECENTLY CONFIRMED WITH THE STATE OF FLORIDA |
| | DEPARTMENT OF AGRICULTURE AND CONTRACTORS LICENSING |
| | BOARD. |
| | |
| | ** PLEASE KNOW FOR INFORMATIONAL PURPOSE, THE GENERATOR |
| | CHECK LIST FROM 2006 IS NO LONGER ACCURATE. SOME ITEMS |
| | ARE CURRENTLY BEING REVISED. |
| | |
| | 2) NOTE: PLEASE COORDINATE PAPERWORK AS SUBMITTED. |
| | PLEASE SEE MANUFACTURES SPECS/CURT SHEETS FROM GENERAC |
| | ATTACHED CLEARLY SHOWS A SEPARATE TRANSFER PANEL WITH |
| | SUB BRANCH CIRCUITS HOWEVER THERE IS ALSO THE SHEETS |
| | FOR A NEW DOUBLE POLE/DOUBLE THROW SAFETY SWITCH. |
| | 110.3, 90.7, 702.6 ETC |
| | |
| | 3) NOTE: PLEASE SHOW A LAYOUT ON PLANS THE LOCATION OF |
| | ALL ELECTRICAL EQUIPMENT. THE RISER DOES NOT INDICATE |
| | WHICH EQUIPMENT IS INSIDE, OUTSIDE, IN ROOMS, ETC. |
| | SEVERAL ITEMS CAN NOT BE VERIFIED AT THIS TIME FOR CODE |
| | COMPLIANCE. |
| | 110.26, 240.24, 408.17 ETC |
| | FBC 106.1.2 |
| | |
| | 4) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR NEW SERVICE |
| | MAINS AND EQUIPMENT. |
| | 110.9 |
| | FBC 106.3.5.4, 106.1.2 |
| | |
| | 5) NOTE: PLEASE SHOW THE GROUNDING ELECTRODE SYSTEM PER |
| | 250.50. THE CWP MAY NOT BE THE ONLY ATTACHMENT. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |