Plan Review Notes
Plan Review Notes For Permit 08050570
Permit Number 08050570
Review Stop E
Sequence Number 1
Notes
Date Text
2008-05-28 10:35:58** DENIED **
  
 1) NOTE:PLEASE KNOW PER FS 527.02 THE PRIMARY
 GENERATOR PERMIT SHALL BE APPLIED FOR UNDER LICENSES AS
 REQUIRED. MAY NO LONGER USE THE U-# ASSOCIATED WITH THE
 ELECTRICAL CONTRACTOR. THE ELECTRICAL LICENSE NUMBER
 STILL MAY BE USED FOR THE ELECTRICAL SUB-PERMIT. THIS
 HAS BEEN RECENTLY CONFIRMED WITH THE STATE OF FLORIDA
 DEPARTMENT OF AGRICULTURE AND CONTRACTORS LICENSING
 BOARD.
  
 ** PLEASE KNOW FOR INFORMATIONAL PURPOSE, THE GENERATOR
 CHECK LIST FROM 2006 IS NO LONGER ACCURATE. SOME ITEMS
 ARE CURRENTLY BEING REVISED.
  
 2) NOTE: PLEASE COORDINATE PAPERWORK AS SUBMITTED.
 PLEASE SEE MANUFACTURES SPECS/CURT SHEETS FROM GENERAC
 ATTACHED CLEARLY SHOWS A SEPARATE TRANSFER PANEL WITH
 SUB BRANCH CIRCUITS HOWEVER THERE IS ALSO THE SHEETS
 FOR A NEW DOUBLE POLE/DOUBLE THROW SAFETY SWITCH.
 110.3, 90.7, 702.6 ETC
  
 3) NOTE: PLEASE SHOW A LAYOUT ON PLANS THE LOCATION OF
 ALL ELECTRICAL EQUIPMENT. THE RISER DOES NOT INDICATE
 WHICH EQUIPMENT IS INSIDE, OUTSIDE, IN ROOMS, ETC.
 SEVERAL ITEMS CAN NOT BE VERIFIED AT THIS TIME FOR CODE
 COMPLIANCE.
 110.26, 240.24, 408.17 ETC
 FBC 106.1.2
  
 4) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR NEW SERVICE
 MAINS AND EQUIPMENT.
 110.9
 FBC 106.3.5.4, 106.1.2
  
 5) NOTE: PLEASE SHOW THE GROUNDING ELECTRODE SYSTEM PER
 250.50. THE CWP MAY NOT BE THE ONLY ATTACHMENT.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]