| 2008-06-03 08:37:36 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | 1. SHEET MEP-1 SANITARY RISER DIAGRAM: PLEASE CORRECT |
| | THE FOLLOWING PER FBC-2004 PLUMBING SECTIONS. |
| | |
| | A} TUB LOCATED IN BATHROOM BY BEDROOM #2 AND #3 NEEDS |
| | A VENT AND A WATER SEAL TRAP. PER SECTION 901.2.1 VENT |
| | REQUIRED AND SECTION 1002.1 FIXTURE TRAPS. |
| | |
| | B} TUB AND SHOWER IN MASTER BATH REQUIRE A VENT. PER |
| | SECTION 901.2.1 VENT REQUIRED. |
| | |
| | C} CLEARLY INDICATE THAT THE CLEANOUT AT THE JUNCTION |
| | OF THE BUILDING DRAIN AND BUILDING SEWER IS A TWO-WAY |
| | CLEANOUT. PER SECTION 708.3.5 BUILDING DRAIN AND |
| | BUILDING SEWER JUNCTION. |
| | |
| | D} PLEASE DELETE THE FOLLOWING FROM THE PLANS |
| | "RECONNECT TO EXIST. SEPTIC TANK AND DRAINFIELD" DUE TO |
| | THE CITY OF W.P.B. HAVING A SANITARY SEWER SYSTEM. PER |
| | SECTION 701.1 SCOPE. |
| | |
| | 2. ENERGY CALCULATIONS NEED TO SIGNED BY OWNER/AGENT. |
| | PER FBC-2004 SECTION 13-103.3. BUILDING PERMITS. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |