Plan Review Notes
Plan Review Notes For Permit 08050559
Permit Number 08050559
Review Stop M
Sequence Number 1
Notes
Date Text
2008-05-23 11:58:23PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 15 IS TAKING THE CROSS
 VENTILATION CREDIT. THE PLANS SUBMITTED SHOW THE
 ADDITION IS NOT QUALIFIED TO TAKE THIS CREDIT. PLEASE
 SHOW HOW THE HOUSE MEETS THE REQUIREMENTS OF 2004 FBC
 13-607.1.A.3.1 CROSS VENTILATION CREDIT .
 HOUSES FOR WHICH CREDIT IS CLAIMED FOR CROSS
 VENTILATION IN ACCORDANCE WITH THE CRITERIA IN SECTION
 13-607.2.A.3.3 SHALL HAVE PROVIDED OPERABLE APERTURE
 AREAS TOTALING A MINIMUM OF 12 PERCENT OF THE FLOOR
 AREA OF THE ROOM FOR ALL PRIMARY LIVING AREAS AND MAIN
 BEDROOMS.
 INSECT SCREENS SHALL BE PROVIDED FOR ALL WINDOWS AND
 DOORS TO BE CONSIDERED OPERABLE APERTURE AREA. ALL
 SCREENED ENTRY DOORS AND INTERIOR DOORS IN THE
 VENTILATED AREAS SHALL BE PROVIDED WITH EITHER (1)
 MECHANICALLY ATTACHED DOOR STOPS (OR SIMILAR DEVICES)
 TO HOLD THE DOOR IN AN OPEN POSITION OR (2) OPERABLE
 LOUVERS.
 THE TOTAL APERTURE AREA SHALL BE PROVIDED BY A MINIMUM
 OF TWO DISTINCT WINDOWS. EACH WINDOW SHALL PROVIDE NOT
 MORE THAN 70 PERCENT OF THE TOTAL APERTURE AREA. THE
 WINDOWS (OR SLIDING GLASS DOORS) SHALL BE PLACED IN
 ADJACENT OR OPPOSITE WALLS. THE WINDOWS MAY BE PLACED
 ON A SINGLE OUTSIDE WALL IF WING WALLS ARE USED. WHERE
 WING WALLS ARE INCLUDED IN THE BUILDING DESIGN FOR
 VENTILATION PURPOSES, THEY SHALL BE PLACED BETWEEN
 WINDOWS TO CREATE A HIGH-PRESSURE AND A LOW-PRESSURE
 ZONE ON EACH WINDOW. WING WALLS SHALL EXTEND FROM THE
 GROUND TO EVE HEIGHT, BE LOCATED ON THE WINDWARD SIDE
 OF THE BUILDING, AND EXTEND OUTWARD FROM THE BUILDING A
 DISTANCE AT LEAST EQUAL TO ONE-HALF THE WIDTH OF THE
 WINDOW.
 NOTE: THIS TECHNIQUE IS EFFECTIVE ONLY FOR AREAS WHICH
 EXPERIENCE SIGNIFICANT AND CONTINUOUS WINDS DURING THE
 COOLING MONTHS
  
 ** ALSO SUBMIT DOCUMANTION SHOWING THAT THIS LOCATION
 SUPORTS THE NOTE ABOVE REGARDING WINDS.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 3)A/C SYSTEM MODEL NUMBERS LISTED ON THE A/C
 EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI
 DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI
 CERTIFICATE, SEE 2004 FBC 13-407.1.ABC.3.1.1 OR
 13-607.1.ABC.3.1.1.
  
 4) SHOW THE SEER OF THE A/C SYSTEM IN THE EQUIPMENT
 SCHEDULE ON MECHANICAL PLAN, SEE 2004 FBC
 13-607.1.ABC.3.2.1.
  
 5)SHOW THE HEATER KW IN THE EQUIPMENT SCHEDULE ON
 MECHANICAL PLAN, SEE 2004 FBC 13-608.1.ABC.3.2.2.
  