Plan Review Notes
Plan Review Notes For Permit 08050559
Permit Number 08050559
Review Stop E
Sequence Number 1
Notes
Date Text
2008-05-22 14:36:23 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER
 1AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
 1} VERIFY THAT NO EQUIPMENT GROUND EXISTS BETWEEN THE
 DISCONNECT AND PANEL "A", AS THIS IS A VIOLATION OF
 250.122. SHEET MEP-2, RISER DIAGRAM, THIS MAY GENERATE
 MORE COMMENTS.
  
 2} VERIFY THERE IS A SECONDGROUNDING ELECTRODE
 CONDUCTOR AT PANEL "A", THAT VIOLATES 250.24(A)(5), AND
 WOULD NEED TO BE DISCONNECTED.
  
 3} PANEL "A" LISTS #3 CU FEEDERS FOR PANEL "B", THE
 RISER INDICATES #4CU.SEE 310.15 (B)(6) FOR CONDUCTORS
 THAT QUALIFY FOR TABLE 310.15 (B)(6).
  
 4} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED. *LOCATE SAME ON
 THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
  