| Plan Review Notes For Permit 08050559 |
| Permit Number |
08050559 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-05-22 14:36:23 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER | | | 1AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | | | | 1} VERIFY THAT NO EQUIPMENT GROUND EXISTS BETWEEN THE | | | DISCONNECT AND PANEL "A", AS THIS IS A VIOLATION OF | | | 250.122. SHEET MEP-2, RISER DIAGRAM, THIS MAY GENERATE | | | MORE COMMENTS. | | | | | | 2} VERIFY THERE IS A SECONDGROUNDING ELECTRODE | | | CONDUCTOR AT PANEL "A", THAT VIOLATES 250.24(A)(5), AND | | | WOULD NEED TO BE DISCONNECTED. | | | | | | 3} PANEL "A" LISTS #3 CU FEEDERS FOR PANEL "B", THE | | | RISER INDICATES #4CU.SEE 310.15 (B)(6) FOR CONDUCTORS | | | THAT QUALIFY FOR TABLE 310.15 (B)(6). | | | | | | 4} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN | | | INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS | | | SHALL BE INTERCONNECTED AND HARD WIRED. *LOCATE SAME ON | | | THE PLAN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|