| Notes |
| Date |
Text |
| 2008-06-19 15:55:15 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.SEE SHEET 8.THE SHUTTER MOUNTING CONNECTION TYPE | | | ON THE INSTALLATION SCHEDULE SHOULD CORRELATE WITH THE | | | NAMING CONVENTION USED ON THIS PAGE FOR WOOD SUBSTRATE | | | FOR OPENINGS 11 AND 12 (FOR INSTANCE, ALTERNATIVE 1, | | | THROUGH ALTERNATIVE 7).ON THE INSTALLATION SCHEDULE | | | YOU HAVE SPECIFIED 12" SPACING, BUT MOST OF THE | | | CONNECTION TYPES REQUIRE 6" SPACING.PLEASE REVISE | | | INSTALLATION SCHEDULE. | | | | | | 2ND REVIEW, 12" FOR CONCRETE BLOCK SPECIFIED ON THE | | | INSTALLATION SCHEDULE, BUT SEE THE PRODUCT APPROVAL. | | | CONNECTION TYPE 1 REQUIRES A CONCRETE SUBSTRATE; THERE | | | IS A "-' IN THE COLUMN MARKED "TO MASONRY".PLEASE | | | REVISE. | | | | | | 2-3.ADDRESSED. | | | |
|