2008-05-21 15:25:45GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PERMIT INFORMATION INDICATES EXISTING NATURAL GAS TO
 SAID RESIDENCE.THE FOLLOWING CORRECTIONS/INFORMATION
 ARE REQUIRED FOR GAS PLAN REVIEW TO MEET CODE
 COMPLIANCE.
  
 1. CLEARLY INDICATE ON THE RESUBMITTED PLANS THE
 LONGEST LENGTH FROM THE NEW METER LOCATION TO THE
 FARTHEST APPLIANCE ON THE EXISTING GAS SYSTEM. PER
 FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
  
 2. CLEARLY INDICATE THE TOTAL BTU'S OF THE EXISTING
 GAS SYSTEM ON THE RESUBMITTED PLANS. PER FBC-2004 FUEL
 GAS SECTION 401.1 SCOPE.
  
 3. CLEARLY INDICATE THE DELIVERY PRESSURE OF THE
 NATURAL GAS SYSTEM ON THE RESUBMITTED PLANS (0.5 PSI OR
 2 PSI). PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
  
 END OF COMMENTS:
  