| 2008-05-21 15:25:45 | GAS PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | PERMIT INFORMATION INDICATES EXISTING NATURAL GAS TO | | | SAID RESIDENCE.THE FOLLOWING CORRECTIONS/INFORMATION | | | ARE REQUIRED FOR GAS PLAN REVIEW TO MEET CODE | | | COMPLIANCE. | | | | | | 1. CLEARLY INDICATE ON THE RESUBMITTED PLANS THE | | | LONGEST LENGTH FROM THE NEW METER LOCATION TO THE | | | FARTHEST APPLIANCE ON THE EXISTING GAS SYSTEM. PER | | | FBC-2004 FUEL GAS SECTION 401.1 SCOPE. | | | | | | 2. CLEARLY INDICATE THE TOTAL BTU'S OF THE EXISTING | | | GAS SYSTEM ON THE RESUBMITTED PLANS. PER FBC-2004 FUEL | | | GAS SECTION 401.1 SCOPE. | | | | | | 3. CLEARLY INDICATE THE DELIVERY PRESSURE OF THE | | | NATURAL GAS SYSTEM ON THE RESUBMITTED PLANS (0.5 PSI OR | | | 2 PSI). PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|