| Plan Review Notes For Permit 08050546 |
| Permit Number |
08050546 |
|
| Review Stop |
B |
| Sequence Number |
9 |
|
| Notes |
| Date |
Text |
| 2009-04-01 09:55:06 | 2004 FBC | | | REVISED PLAN SHEETS | | | | | | DENIED BY BUILDING | | | | | | 1) THE REVISED PLANS THAT WERE SUBMITTED HAVE NOT BEEN | | | SIGNED AND SEALED BY THE ENGINEER AS REQUIRED BY FS 471 | | | AND FAC 61G15-23.002. | | | | | | 2) SHEET A3 SPECIFIES A 10' CEILING HEIGHT FOR THE | | | THIRD FLOOR AND THE ELEVATIONS ON A4, A5, AND A6 SHOW | | | 9'-1" BEAM HEIGHTS. PLEASE CLARIFY. | | | | | | 3) SHEET A13 SHOWS VAULTED CEILINGS AND THE TRUSS | | | DRAWINGS THAT WERE SUBMITTED ARE FOR FLAT CEILINGS. | | | PLEASE CORRECT. | | | | | | 4) ON SHEET A10 THE LOCATION OF THE COLUMNS AND ROOF | | | OVERHANG FOR THE EAST SIDE OF THE FRONT PORCH DOES NOT | | | MATCH THE OTHER REVISED SHEETS. PLEASE CORRECT. | | | | | | 5) THE EAST SIDE OF THE PORCH ON THE REVISED SHEETS | | | APPEARS TO ENCROACH INTO THE REQUIRED 25' SETBACKS. | | | THIS REQUIRES ZONING APPROVAL. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|