Plan Review Notes
Plan Review Notes For Permit 08050546
Permit Number 08050546
Review Stop B
Sequence Number 9
Notes
Date Text
2009-04-01 09:55:062004 FBC
 REVISED PLAN SHEETS
  
 DENIED BY BUILDING
  
 1) THE REVISED PLANS THAT WERE SUBMITTED HAVE NOT BEEN
 SIGNED AND SEALED BY THE ENGINEER AS REQUIRED BY FS 471
 AND FAC 61G15-23.002.
  
 2) SHEET A3 SPECIFIES A 10' CEILING HEIGHT FOR THE
 THIRD FLOOR AND THE ELEVATIONS ON A4, A5, AND A6 SHOW
 9'-1" BEAM HEIGHTS. PLEASE CLARIFY.
  
 3) SHEET A13 SHOWS VAULTED CEILINGS AND THE TRUSS
 DRAWINGS THAT WERE SUBMITTED ARE FOR FLAT CEILINGS.
 PLEASE CORRECT.
  
 4) ON SHEET A10 THE LOCATION OF THE COLUMNS AND ROOF
 OVERHANG FOR THE EAST SIDE OF THE FRONT PORCH DOES NOT
 MATCH THE OTHER REVISED SHEETS. PLEASE CORRECT.
  
 5) THE EAST SIDE OF THE PORCH ON THE REVISED SHEETS
 APPEARS TO ENCROACH INTO THE REQUIRED 25' SETBACKS.
 THIS REQUIRES ZONING APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]