Plan Review Notes
Plan Review Notes For Permit 08050546
Permit Number 08050546
Review Stop B
Sequence Number 7
Notes
Date Text
2009-02-09 14:49:52TRUSS LAYOUT AND DRAWINGS SUBMITTAL
  
 DENIED BY BUILDING
  
 1) THE SECOND FLOOR TRUSS LAYOUT DOES NOT MATCH THE
 APPROVED PLANS. THE LOWER ROOF ON THE EAST ELEVATION IS
 SHOWN THE LENGTH OF THE STRUCTURE ON THE TRUSS LAYOUT
 AND THE APPROVED PLANS HAVE IT SLIGHTLY LONGER THAN THE
 GARAGE DOOR OPENING. PLEASE CORRECT.
  
 2) THE UPPER ROOF TRUSS DRAWINGS HAVE A BOTTOM CORD
 LIVE LOAD OF 0 PSF AND THE TRUSS LAYOUT SPECIFIES A
 BOTTOM CORD LIVE LOAD OF 10 PSF. FBC R305.1 REQUIRES A
 LIVE LOAD OF 10 PSF FOR ATTICS WITHOUT STORAGE. PLEASE
 CORRECT.
  
 3) THE MEAN HEIGHT OF THE STRUCTURE IS SPECIFIED AS 15
 FT ON THE UPPER ROOF TRUSS DRAWING FOR TRUSS UJ3 AND
 THE THREE STORY STRUCTURE SHOWN ON THE PLANS HAS A MEAN
 ROOF HEIGHT OF 35 FT. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714