| Plan Review Notes For Permit 08050546 |
| Permit Number |
08050546 |
|
| Review Stop |
B |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2009-01-13 10:50:15 | TRUSS LAYOUT AND DRAWINGS SUBMITTAL | | | | | | DENIED BY BUILDING | | | | | | 1) TRUSS LAYOUT IS REQUIRED TO BE REVIEWED AND APPROVED | | | IN WRITING BY THE DESIGNER OF RECORD FOR THE STRUCTURE. | | | | | | 2) THE SECOND FLOOR TRUSS LAYOUT DOES NOT MATCH THE | | | APPROVED PLANS. THE LOWER ROOF ON THE EAST ELEVATION IS | | | SHOWN THE LENGTH OF THE STRUCTURE ON THE TRUSS LAYOUT | | | AND THE APPROVED PLANS HAVE IT SLIGHTLY LONGER THAN THE | | | GARAGE DOOR OPENING. PLEASE REVISE. | | | | | | 3) THE FG2 FLOOR GIRDER IS SHOWN ON THE THIRD FLOOR | | | TRUSS LAYOUT EXTENDING FROM EXTERIOR WALL TO EXTERIOR | | | WALL. THE THIRD FLOOR FRAMING ON THE APPROVED PLANS | | | SHOW THIS GIRDER STOPPING AT THE BEARING WALL OF THE | | | STAIR OPENING. PLEASE COORDINATE DRAWINGS. | | | | | | 4) THE ROOF TRUSS DRAWINGS HAVE A BOTTOM CORD LIVE LOAD | | | OF 0 PSF AND THE TRUSS LAYOUT SPECIFIES A BOTTOM CORD | | | LIVE LOAD OF 10 PSF. FBC R305.1 REQUIRES A LIVE LOAD OF | | | 10 PSF FOR ATTICS WITHOUT STORAGE. PLEASE CORRECT. | | | | | | 5) THE MEAN HEIGHT OF THE STRUCTURE IS SPECIFIED AS 15 | | | FT ON THE TRUSS DRAWINGS AND THE THREE STORY STRUCTURE | | | SHOWN ON THE PLANS HAS A MEAN ROOF HEIGHT OF 35 FT. | | | PLEASE CORRECT. | | | | | | 6) THE TRUSS DRAWINGS SPECIFY AN UPLIFT OF 667# FOR THE | | | UG1 GIRDER TRUSS AND THE U3 COMMON TRUSS HAS AN UPLIFT | | | OF 1114#. PLEASE CHECK THESE CALCULATIONS AND EXPLAIN | | | HOW THIS IS POSSIBLE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|