| Plan Review Notes For Permit 08050546 |
| Permit Number |
08050546 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2008-11-26 13:17:20 | 2004 FBC W/2007 REVISIONS | | | NSFD | | | | | | REVISED PLAN SHEETS A1, A2 AND A3 ARE DENIED. | | | | | | 1) THE PLANS ARE MISSING INFORMATION. PORTIONS OF THE | | | SCHEDULES AND TABLES ARE MISSING FROM THESE PAGES. | | | | | | 2) THE NEW DOUBLE FRENCH DOOR (1A) SHOWN ON SHEET 1A IS | | | NOT LISTED IN THE DOOR SCHEDULE. PLEASE REVISE. | | | R301.2.1 | | | | | | 3) THE DOOR FOR THE GARAGE TO THE RESIDENCE IS REQUIRED | | | TO COMPLY WITH R309.1 OPENING PROTECTION. OPENINGS FROM | | | A PRIVATE GARAGE DIRECTLY INTO A ROOM USED FOR SLEEPING | | | PURPOSES SHALL NOT BE PERMITTED. OTHER OPENINGS BETWEEN | | | THE GARAGE AND RESIDENCE SHALL BE EQUIPPED WITH SOLID | | | WOOD DOORS NOT LESS THAN 13/8 INCHES (35 MM) IN | | | THICKNESS, SOLID OR HONEYCOMB CORE STEEL DOORS NOT LESS | | | THAN 13/8 INCHES (35 MM) THICK, OR 20-MINUTE FIRE-RATED | | | DOORS. | | | | | | 4) A SECOND FLOOR WINDOW AND FIRST FLOOR DOORS HAVE | | | BEEN MOVED OR CHANGED. REVISED ELEVATIONS REFLECTING | | | THE CHANGES ARE REQUIRED. FBC 106.1.1* CITY AMENDMENTS | | | | | | 5) A WASHER AND DRYER HAS BEEN ADDED TO THE FIRST FLOOR | | | AND HAS NOT BEEN CLOUDED TO INDICATE THE REVISION. FBC | | | 106.1.3* CITY AMENDMENTS. | | | | | | 6) ON SHEET A3, IT APPEARS THAT THE SHOWER HAS BEEN | | | ELIMINATED FROM BATH ROOM #2. PLEASE CLARIFY. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|