Plan Review Notes
Plan Review Notes For Permit 08050546
Permit Number 08050546
Review Stop B
Sequence Number 5
Notes
Date Text
2008-11-26 13:17:202004 FBC W/2007 REVISIONS
 NSFD
  
 REVISED PLAN SHEETS A1, A2 AND A3 ARE DENIED.
  
 1) THE PLANS ARE MISSING INFORMATION. PORTIONS OF THE
 SCHEDULES AND TABLES ARE MISSING FROM THESE PAGES.
  
 2) THE NEW DOUBLE FRENCH DOOR (1A) SHOWN ON SHEET 1A IS
 NOT LISTED IN THE DOOR SCHEDULE. PLEASE REVISE.
 R301.2.1
  
 3) THE DOOR FOR THE GARAGE TO THE RESIDENCE IS REQUIRED
 TO COMPLY WITH R309.1 OPENING PROTECTION. OPENINGS FROM
 A PRIVATE GARAGE DIRECTLY INTO A ROOM USED FOR SLEEPING
 PURPOSES SHALL NOT BE PERMITTED. OTHER OPENINGS BETWEEN
 THE GARAGE AND RESIDENCE SHALL BE EQUIPPED WITH SOLID
 WOOD DOORS NOT LESS THAN 13/8 INCHES (35 MM) IN
 THICKNESS, SOLID OR HONEYCOMB CORE STEEL DOORS NOT LESS
 THAN 13/8 INCHES (35 MM) THICK, OR 20-MINUTE FIRE-RATED
 DOORS.
  
 4) A SECOND FLOOR WINDOW AND FIRST FLOOR DOORS HAVE
 BEEN MOVED OR CHANGED. REVISED ELEVATIONS REFLECTING
 THE CHANGES ARE REQUIRED. FBC 106.1.1* CITY AMENDMENTS
  
 5) A WASHER AND DRYER HAS BEEN ADDED TO THE FIRST FLOOR
 AND HAS NOT BEEN CLOUDED TO INDICATE THE REVISION. FBC
 106.1.3* CITY AMENDMENTS.
  
 6) ON SHEET A3, IT APPEARS THAT THE SHOWER HAS BEEN
 ELIMINATED FROM BATH ROOM #2. PLEASE CLARIFY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]