| Date |
Text |
| 2008-08-29 14:41:48 | PLUMBING PLAN REVIEW: |
| | DENIED **2ND TIME: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND |
| | WITH THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS |
| | THE DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. SHEET M4 UNIT THREE FIRST AND SECOND FLOOR SANATRY |
| | PLUMBING RISERS: PLEASE CORRECT THE FOLLOWING PER |
| | FBC-2004 PLUMBING THE FOLLOWING SECTIONS. |
| | |
| | A} KITCHEN SINK REQUIRES A VENT. PLEASE CLEARLY |
| | INDICATE A VENT ON THE RESUBMITTAL. PER SECTION 901.2.1 |
| | VENTING REQUIRED. |
| | |
| | B} KITCHEN SINK DOES NOT REFLECT THE FLOOR PLAN. SHEET |
| | A2 UNIT THREE FLOOR PLAN INDICATES A DOUBLE BOWL |
| | KITCHEN SINK WITH A DISHWASHER, HOWEVER THE SANITARY |
| | RISER ON SHEET M4 IS ONLY INDICATING A SINGLE BOWL |
| | SINK. AT A MINIMUM THE RISER DIAGRAM SHALL REFLECT THE |
| | FLOOR PLAN. PER SECTION 701.1 SCOPE. |
| | |
| | C} THE SOIL STACK FOR THE FIRST, SECOND AND THIRD FLOOR |
| | REQUIRES A CLEANOUT AT THE BASE OF THE STACK. PER |
| | 708.3.4 BASE OF STACK. |
| | |
| | D} CLEARLY INDICATE THAT A TWO-WAY CLEANOUT SHALL BE |
| | INSTALLED AT THE JUNCTION OF THE BUILDING DRAIN AND |
| | BUILDING SEWER. PER SECTION 708.3.5 BUILDING DRAIN AND |
| | BUILDING SEWER JUCTION. |
| | |
| | **RESPONSE NOTED, HOWEVER THE RESUBMITTED PLANS DO NOT |
| | HAVE SHEET M-4 PLUMBING RISERS IN THEM TO REVIEW. |
| | PLEASE KNOW THAT TWO COPIES OF SHEET M-4 PLUMBING |
| | RISERS ARE REQUIRED FOR PLUMBING PLAN REVIEW. PER |
| | (W.P.B. AS AMENDED) SECTION 106.1 SUBMITTAL DOCUMENTS. |
| | |
| | 2."OK" COMMENT ADDRESSED. |
| | |
| | 3. "OK" COMMENT ADDRESSED. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |