| Plan Review Notes For Permit 08050546 |
| Permit Number |
08050546 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-09-04 13:28:45 | PLAN REVIEW STATUS WILL BE CHANGED TO P WHEN IMPACT | | | FEES ARE PAID AND STAMPED PLANS AND PAID RECEIPT ARE | | | SUBMITTED. | | | | | | BUILDING PROVISO | | | | | | PROVIDE CARBON MONOXIDE ALARMS. PER FS 553.885 CARBON | | | MONOXIDE ALARM REQUIRED.-- EVERY BUILDING FOR WHICH A | | | BUILDING PERMIT IS ISSUED FOR NEW CONSTRUCTION ON OR | | | AFTER JULY 1, 2008, AND HAVING A FOSSIL-FUEL-BURNING | | | HEATER OR APPLIANCE, A FIREPLACE, OR AN ATTACHED GARAGE | | | SHALL HAVE AN APPROVED OPERATIONAL CARBON MONOXIDE | | | ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM USED FOR | | | SLEEPING PURPOSES. PLEASE COMPLY. | | | | | | SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR 16' X 7' | | | GARAGE DOOR WITH ADEQUATE DESIGN PRESSURES. ( + 43.0, | | | -52.2 ). |
|