| 2008-06-02 16:03:59 | PLUMBING PLAN REVIEW UNIT THREE: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | 1. SHEET M4 UNIT THREE FIRST AND SECOND FLOOR SANATRY |
| | PLUMBING RISERS: PLEASE CORRECT THE FOLLOWING PER |
| | FBC-2004 PLUMBING THE FOLLOWING SECTIONS. |
| | |
| | A} KITCHEN SINK REQUIRES A VENT. PLEASE CLEARLY |
| | INDICATE A VENT ON THE RESUBMITTAL. PER SECTION 901.2.1 |
| | VENTING REQUIRED. |
| | |
| | B} KITCHEN SINK DOES NOT REFLECT THE FLOOR PLAN. SHEET |
| | A2 UNIT THREE FLOOR PLAN INDICATES A DOUBLE BOWL |
| | KITCHEN SINK WITH A DISHWASHER, HOWEVER THE SANITARY |
| | RISER ON SHEET M4 IS ONLY INDICATING A SINGLE BOWL |
| | SINK. AT A MINIMUM THE RISER DIAGRAM SHALL REFLECT THE |
| | FLOOR PLAN. PER SECTION 701.1 SCOPE. |
| | |
| | C} THE SOIL STACK FOR THE FIRST, SECOND AND THIRD FLOOR |
| | REQUIRES A CLEANOUT AT THE BASE OF THE STACK. PER |
| | 708.3.4 BASE OF STACK. |
| | |
| | D} CLEARLY INDICATE THAT A TWO-WAY CLEANOUT SHALL BE |
| | INSTALLED AT THE JUNCTION OF THE BUILDING DRAIN AND |
| | BUILDING SEWER. PER SECTION 708.3.5 BUILDING DRAIN AND |
| | BUILDING SEWER JUCTION. |
| | |
| | 2. PER (W.P.B. AS AMENDED) SECTION 106.1 SUBMITTAL |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS, SPECIAL INSPECTION |
| | AND STRUCTURAL OBSERVATION PROGRAMS, AND OTHER DATA |
| | SHALL BE SUBMITTED IN TWO OR MORE SETS WITH EACH |
| | APPLICATION FOR A PERMIT. |
| | NOTE: ONLY ONE SET OF ENERGY AND COOLING CALCULATIONS |
| | WAS SUBMITTED. |
| | |
| | 3. RESUBMITTED ENERGY CALCULATIONS NEED TO BE SIGNED BY |
| | THE PREPARER AND THE OWNER/AGENT. PER FBC-2004 |
| | 13-600.3.ABC.2 AND 13-600.3.A. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |