Plan Review Notes
Plan Review Notes For Permit 08050546
Permit Number 08050546
Review Stop M
Sequence Number 1
Notes
Date Text
2008-05-23 16:40:09PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 11B IS SHOWING FOR THIRD
 FLOOR SYSTEM THE SUPPLY AND RETURN AIR DUCTS IN A
 CONDITIONED SPACE AND THE AIR HANDLER INTERIOR, THE
 PLANS PAGE M3 SHOWS IT ALL TO BE IN THE ATTIC. PLEASE
 CORRECT, PER 2004 FBC 13-600.3.A.
  
 2) PLEASE SUBMIT TWO COPIES OF THE ENERGY AND COOLING
 LOAD CALCULATIONS, AS ONLY ONE COPY WAS SUBMITTED. PER
 2004 W.P.B. AMEND. 106.1.
  
 3) WHEN RESUBMITTING THE REVISED ENERGY CALCULATIONS
 THEY WILL NEED TO BE SIGNED BY THE PREPARER AND THE
 OWNER/AGENT, PER 2004 FBC 13-600.3.ABC.2 AND
 13-600.3.A.
  
 4) PLEASE LABEL ALL A/C SYSTEMS AND EQUIPMENT AS #1 OR
 #2, SEE RED LINE ON PLANS M1, M2, AND M3. PER 2004 FBC
 106.1.1.
  
 5)A/C SYSTEM #2 MODEL NUMBERS UAND-018JAZ WITH
 UHLA-HM3617JA LISTED ON THE A/C EQUIPMENT SCHEDULE
 COULD NOT BE FOUND ON THE ARI DIRECTORY WEB-SITE. I
 BELIEVE THE AIR HANDLER MODEL NUMBER YOU NEED IS
 UHLA-HM2417 (SEE ATTACHED ARI CERTIFICATE). PLEASE
 CORRECT OR SUBMIT AN ARI CERTIFICATE, SEE 2004 FBC
 13-407.1.ABC.3.1.1 OR 13-607.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]