 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER
 1AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
 1} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
 2} THERE IS ONLY ONE A/C SYSTEM ON THE PANEL SCHEDULE ,
 SHEET E1. SHEET M1 HAS SPECIFICATIONS FOR TWO UNITS,
 NEITHER OF WHICH DOES THE WATTAGES FOR THE HEAT STRIP
 CORRELATE. RECALCULATE THE LOAD AND CHANGE THE PANEL
 SCHEDULE TO INDICATE THE INTENDED INSTALLATION.
  
 3} CIRCUIT #10 HAS NO OCP LISTED.
  
 4} THERE IS POOL EQUIPMENT LISTED ON THE PANEL
 SCHEDULE. IS THIS A GENERIC SCHEDULE INTENDED FOR ALL
 THREE UNITS OR A SCHEDULE FOR UNIT #3 THAT IS THE
 PROJECT ON THE APPLICATION DESCRIPTION? SEE 210.25 FOR
 BRANCH CIRCUIT RESTRICTIONS APPLYING TO COMMON AREAS.
  
 5} CIRCUIT 2,4 HAS AN OCP OF 40 AMPS FOR THE 8000 WATT
 WATER HEATER. SEE ARTICLE 422.13 CONTINUOUS LOAD.
 (8000/240= 33.33 X 125%= 41.6AMPS).
  
 6} SHEET E2 NEEDS TWO RECEPTACLES TO COMPLY WITH
 210.52(C)(1).
  
 7} THE MASTER BEDROOM AND BEDROOM #2 ON SHEET E3 NEED
 ADDED RECEPTACLES TO COMPLY WITH 210.52(A)(1) & (2).
 SEE REVIEWED SET FOR APPROXIMATE LOCATION.
  
 8} A RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3) ARE
 REQUIRED IN THE ATTIC WHERE THE AHU IS TO BE INSTALLED,
 (SHOWN ON SHEET M3).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718