| Plan Review Notes For Permit 08050543 |
| Permit Number |
08050543 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-06-25 16:08:21 | *****DENIED***** | | | | | | | | | | | | 1.THE ACTUAL SCOPE OF WORK ADDRESS SHALL BE IN THE | | | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.SEE BLDG | | | EXAMINER'S COMMET # 1F | | | | | | 2.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE | | | WITH EMERGENCY RESPONSE TO THE SAID PROPERTY OR THE | | | VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE | | | LANES, ETC) . | | | | | | 3.PLEASE INDICATE THE USAGE OF THE STATIONARY | | | GENERATOR AS FOR EMERGENCY USE OR STANDBY POWER. | | | | | | 4.THE GENERATOR SHALL BE INSTALLED IN ACCORDANCE WITH | | | NFPA 110, 2002 EDITION. | | | | | | 5.DEPENDING UPON LOCATION OF THE EQUIPMENT, | | | SAFEGUARDS AGAINST MECHANICAL DAMAGE MAY BE REQUIRED | | | AND SHALL BE ILLUSTRATED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|