Plan Review Notes
Plan Review Notes For Permit 08050540
Permit Number 08050540
Review Stop E
Sequence Number 1
Notes
Date Text
2008-06-18 15:37:30** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE VALUE FOR THE COMPLETE SCOPE OF
 WORK INCLUDING ALL EQUIPMENT, DESIGN COST ETC SHALL BE
 INCLUDED EVEN IF ANY EQUIPMENT SUCH AS THE BUILDING,
 GENERATOR ETC IS OWNER SUPPLIED.
 FBC 108.3
  
 2) NOTE: PLEASE BE SURE TO SUBMIT THE MANUFACTURES
 SPECS/CUT SHEETS WHICH ACTUALLY STATE THE MINIMUM
 CLEARANCES. AS REQUIREMENTS FOR OTHER TRADES SUCH AS
 ZONING MAY REQUIRE A WALL OF SOME KIND. THE SET BACKS
 NEED TO BE SHOWN.
 NEED TO ALSO SHOW THE ACTUAL SET BACK FROM PROPERTY
 LINE AS THE MINIMUM WILL ALSO BE REQUIRED FROM PROPERTY
 LINE.
 90.7, 110.3. ETC
 FBC 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 3) NOTE: PLEASE SHOW HOW ANY TRANSFER OF POWER FROM THE
 RECEPTACLE SHOWN ON PLANS TO EQUIPMENT MEETS 701.7.
  
 4) NOTE: PLEASE STATE ON PLANS THE MINIMUM RUN TIMES
 PER FEDERAL CODE OF REGULATIONS TITLE 47, PART 12.2
  
 5) NOTE: PLEASE BE SURE TO DATE PLANS WHEN SIGNING AND
 SEALING PER FS 471.025, 481.221
  
 6) NOTE: PLEASE SHOW HOW THE BREAKER ON THE GENERATOR
 MEETS 701.11B5 FOR THE EXCEPTION OF THE REQUIRED
 DISCONNECT PER 225.361-225.39 FOR FEEDERS.
  
 7) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE PROPOSED ATS. 90.7,110.3, 701.7.
 PLEASE SEE COMMENT #3 ABOVE WHICH WILL ALSO NEED
 SPECS/CUT SHEETS.
  
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]