Plan Review Notes For Permit 08050540
Permit Number 08050540
Review Stop B
Sequence Number 1
Notes
Date Text
2008-06-17 08:43:09BUILDING PLAN REVIEW
 PERMIT: 08050540
 ADD: 6650 45TH ST.
 CONT: SBA NETWORK SERVICES
 TEL: (352)629-1774
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.PLEASE UPDATE THE
 STRUCTURAL ANALYSIS REPORT & THE STRUCTURAL SHEET S-1 &
 T-1.
  
 1F) THE CITY'S ADDRESSING DEPARTMENT HAS DETERMINED
 THAT THE CURRENT ADDRESS IS OUT OF THE CITIES RANGE,
 THE NEW ADDRESS FOR THIS PCN WILL BE 6650 45TH STREET
 AND SHOULD BE USED ON ALL PLANS, PERMIT APPLICATION AND
 CORRESPONDANCE.
  
 2) AMERICAN TOWER ENGINEERING SERVICES -STRUCTURAL
 ANALYSIS REPORT DOES NOT INDICATE THERE CERTIFICATE OF
 AUTHORIZATION NUMBER. 481.219 F.S. CERTIFICATE OF
 AUTHORIZATION. THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ARCHITECT PRACTICING UNDER A FICTITIOUS
 NAME, A CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET.
 WE COULD NOT FIND YOUR COA NUMBER ON THE DEPARTMENT OF
 BUSSINESS & PROFESSIONAL REGULATION WEBSSITE, PLEASE
 PROVIDE. THIS MAY BE ADDED BY HAND.
  
 3) ENGINEER JASON SEAVERSON - AMERICAN TOWER STRUCTURAL
 ANALYSIS REPORT HAS SIGNED AND SEALED THIS DOCUMENT BUT
 MISSING HIS PRINTED NAME AND LICENSE NUMBER, PLEASE
 CORRECT.
 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE:
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 4) ENGINEER JASON SEAVERSON - AMERICAN TOWER STRUCTURAL
 ANALYSIS REPORT DOES NOT INDICATE HOW MANY SHEETS ARE
 WITHIN THE DOCUMENT AND HAS ONLY SIGNED AND SEALED THE
 COVER SHEET, PLEASE CORRECT. 61G15-23.002(2) FL. ADMIN.
 CODE. A COVER SHEET OR INDEX SHEET FOR ENGINEERING
 SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE
 SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION &
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX.
  
 5) STRUCTURAL ANALYSIS REPORT PAGE 1 IT APPEARS THERE
 MAY BE CONFLICTS WITH SECTIONS OF THE CODE: DESIGNS ARE
 TO ASCE 7-02,
  
 5A) THE STRUCTURAL CLASSIFICATION OF THE STRUCTURE IS A
 CLASS II, PLEASE SEE ASCE 7-02 TABLE 1-1,
 COMMUNICATIONS TOWERS ARE LISTED AS A TYPE IV STRUCTURE
 , CELL PHONES ARE USED AS PART OF THE RECOVERY EFFORT
 FOR HIGH WIND EVENTS, PLEASE SEE TABLE 6-1 IMPORTANCE
 FACTOR FOR BUILDING CATEGORY IV= 1.15 NOT THE 1.0
 LISTED .
  
 5B) LOAD CASE IS INDICATED AS 1.2D+1.6W PLEASE SEE
 1605.2 BASIC LOAD COMBINATIONS 0.9D+(1.6W) IS THE MORE
 RESTRICTIVE DESIGN WHICH SHOULD HAVE BEEN USED IN THIS
 CASE. 1605.2.1 WHERE STRENGTH DESIGN OR LOAD AND
 RESISTANCE FACTOR DESIGN IS USED, STRUCTURES AND
 PORTIONS THEREOF SHALL RESIST THE MOST CRITICAL EFFECTS
 FROM THE FOLLOWING COMBINATIONS OF FACTORED LOADS.
  
 PLEASE RUN THE LOADING CALCULATIONS WITH THESE
 ADJUSTMENT FACTORS TO MEET THE CURRENT WIND LOADING
 CRITERIA. THE CALCULATIONS MAY EXCEED THE 5% ADDITIONAL
 GRAVITY LOADS ALLOWED UNDER THE 2004 FBC EXISTING
 BUILDING CODE 903.2, EXCEPTION# 1.
  
 6) PLANS INDICATE ON SHEET T-1 130 MPH WIND ZONE PLEASE
 CORRECT TO 140 MPH SEE FIGURE 1609.
  
 7) SHEET A-3 INDICATES THE USE OF A STATE APPROVED AT&T
 EQUIPMENT SHELTER, PLEASE PROVIDE (2) COPIES OF THE
 STATE STATE APPROVED PLANS FOR MODULAR BUILDINGS 428.1,
 RULE 9B-1 FLORIDA ADMINISTRATIVE CODE AND CHAPTER 553
 FL S S .
  
 8) SHEET S-1:
 8A) FOUNDATION NOTE# 2 INDICATES SOILS TEST ARE TO BE
 COMPLETED, 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 8B) FOUNDATION NOTE # 2 INDECATES THE DESIGN TO THE
 2004 FBC WITH 2006 REVISIONS, PLEASE UPDATE TO THE 2007
 FBC REVISIONS, PLANS SUBMITTED AFTER JULY 1,2007 ARE TO
 BE DESIGNED TO THE 2007 WIND PROVISIONS.
  
 8C) FOUNDATION NOTE# 2 PLEASE REVISE WIND INFORMATION
 TO 140MPH, 3 SECOND GUST ,PLEASE SEE FIGURE 1609.
  
 8D) FOUNDATION NOTE# 2 PLEASE REVISE BUILDING CATEGORY
 TO A CATEGORY IV ASCE 7-02 TABLE 6-1.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.