| Notes |
| Date |
Text |
| 2008-06-05 15:55:14 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | | | | 1. SHT 1 OF 1 INDICATES A 1" WATER SERVICE CONNNECTING | | | TO AN EXISTING HOSE BIBB. VERIFICATION IS REQUIRED FOR | | | THE SIZE OF THE WATER SUPPLY LINE TO THE HOSE BIBB. | | | SECTION 604.3. | | | | | | 2. SHT 1 0F 1 EACH COMMERCIAL BUILDING SHALL HAVE AN | | | RPZV BACKFLOW INSTALLED ON THE WATER SERVICE. SECTION | | | 608.13.2. | | | | | | 3. SHT 1 OF 1 EVERY BUILDING SHALL HAVE A SEPARATE | | | CONNECTION WITH THE SEWER. SECTION 701.3. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | | THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|